GEYA Mini ATS Automatic/Manual Transfer Switch User Manual

Model: 3P-63A-110VAC

ബ്രാൻഡ്: ഗേയ

1. ആമുഖം

This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA Mini ATS Automatic/Manual Transfer Switch, Model 3P-63A-110VAC. This device is designed to automatically or manually switch between two power sources, such as grid power, a generator, or a photovoltaic system, ensuring continuous power supply to your load.

GEYA Mini ATS Automatic/Manual Transfer Switch

Figure 1: GEYA Mini ATS Automatic/Manual Transfer Switch (Model 3P-63A-110VAC)

2 സുരക്ഷാ വിവരങ്ങൾ

Please read and understand all safety warnings and instructions before installing or operating this device. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • ഇൻസ്റ്റാളേഷനും അറ്റകുറ്റപ്പണിയും യോഗ്യതയുള്ള ഉദ്യോഗസ്ഥർ മാത്രമേ നടത്താവൂ.
  • Always disconnect all power sources before working on the switch or connected circuits.
  • വൈദ്യുതാഘാതം തടയാൻ ശരിയായ ഗ്രൗണ്ടിംഗ് ഉറപ്പാക്കുക.
  • വോളിയം പരിശോധിക്കുകtage and current ratings of the switch match your application requirements.
  • നനഞ്ഞതോ നനഞ്ഞതോ ആയ കാലാവസ്ഥയിൽ സ്വിച്ച് പ്രവർത്തിപ്പിക്കരുത്.amp വ്യവസ്ഥകൾ.
  • വോളിയംtage of the common and backup power supply must be 85-110% of the rated voltage.
  • The current cannot be less than 5A, otherwise the coil may overheat or combust.
  • The backup power of the product must be a stable city power, otherwise the product will not switch automatically.

3. ഉൽപ്പന്ന സവിശേഷതകൾ

  • ഡ്യുവൽ പവർ സോഴ്‌സ് കോംപാറ്റിബിലിറ്റി: Designed for automatic or manual conversion between two power supplies (e.g., mains, generator, photovoltaic).
  • ഓവർ-വോളിയംtagഇ, അണ്ടർ-വോളിയംtage Protection (110V/50Hz):
    • അണ്ടർവോൾtage value: 85V, Recovery value: 95V (± 5V)
    • ഓവർ വോൾtage value: 145V, Recovery value: 130V (± 5V)
  • ഓവർ-വോളിയംtagഇ, അണ്ടർ-വോളിയംtage Protection (220V/50Hz):
    • അണ്ടർവോൾtage value: 175V, Recovery value: 195V (± 5V)
    • ഓവർ വോൾtage value: 260V, Recovery value: 240V (± 5V)
  • യാന്ത്രിക സ്വിച്ചിംഗ്: When the normal power supply is abnormal, the device automatically switches to the backup power supply. It switches back to normal power when restored.
  • ഇൻഡിക്കേറ്റർ ലൈറ്റുകൾ: Equipped with indicator lights for both power sources (A and B) to show operational status.
  • Fast Switching: Power switch completed within 100 milliseconds, minimizing power interruptions.
  • ബുദ്ധിപരമായ നിയന്ത്രണം: Features self-restoring, over-voltagഇ, കൂടാതെ അണ്ടർ-വോളിയംtagഇ സംരക്ഷണം.
  • നീണ്ടുനിൽക്കുന്ന നിർമ്മാണം: Utilizes silver contacts and copper terminals for reliability and longevity.
  • DIN റെയിൽ മൗണ്ടിംഗ്: Compatible with universal DIN rail mounting for easy installation.
Function of Automatic Transfer Switch

Figure 2: Explanation of Automatic Transfer Switch Function

Fast Switching and Intelligent Control Features

Figure 3: Fast Switching and Intelligent Control Capabilities

Silver Contacts, Copper Terminals, and Guide Rail Installation

Figure 4: Internal Components and Installation Method

4. How to Choose Your Model

Refer to the table below to select the appropriate ATS model based on your live line voltage and connection requirements.

Model Selection Guide for GEYA ATS

Figure 5: Model Selection Guide

Model Selection Table
Live Line VoltageSuitable for US Voltagഇ സിസ്റ്റംMust Connect with Neutral Lineശുപാർശ ചെയ്യുന്ന ഉൽപ്പന്നം
One Live Line Voltagഇ 110 വി110/230V1 Live line + 1 Neutral lineATS-2P-63A-110V
2 Live line + 1 Neutral lineATS-3P-63A-110V
3 Live line + 1 Neutral lineATS-4P-63A-110V
One Live Line Voltagഇ 230 വി220/400V1 Live line + 1 Neutral lineATS-2P-63A-220V
2 Live line + 1 Neutral lineATS-3P-63A-220V
3 Live line + 1 Neutral lineATS-4P-63A-220V

കുറിപ്പ്: വോളിയംtage of the common and backup power supply must be 85-110% of the rated voltage, and the current cannot be less than 5A, otherwise the coil will heat up or even spontaneously combust. The backup power of the product must be a stable city power, otherwise the product will not switch automatically.

5. ഉൽപ്പന്ന അളവുകൾ

The GEYA Mini ATS is designed for compact installation with universal DIN rail mounting. Refer to the diagram below for detailed dimensions.

GEYA Mini ATS Product Dimensions

Figure 6: Product Dimensions (in mm)

  • മൊത്തത്തിലുള്ള ദൈർഘ്യം: 125 മി.മീ
  • മൊത്തം വീതി: 78.5 മി.മീ
  • മൊത്തത്തിലുള്ള ഉയരം: 103 മി.മീ
  • DIN Rail Mounting Height: 35 മി.മീ
  • Safety Distance S1: ≥ 30 മി.മീ
  • Safety Distance S2: ≥ 203 മി.മീ
Detailed Product Dimensions and Safety Distances

Figure 7: Detailed Dimensions and Safety Clearances

6 സാങ്കേതിക സവിശേഷതകൾ

Below are the technical specifications for the GEYA Mini ATS Automatic/Manual Transfer Switch.

GEYA Mini ATS Technical Parameters

ചിത്രം 8: സാങ്കേതിക പാരാമീറ്റർ പട്ടിക

Technical Specifications (Model 3P-63A-110VAC)
പരാമീറ്റർസ്പെസിഫിക്കേഷൻ (63A)സ്പെസിഫിക്കേഷൻ (100A)
Rated current Ie A63എ100എ
ഇൻസുലേഷൻ വോള്യംtagഇ യുഐഎസി 690 വി
ഇൻപുട്ട് വോളിയംtagഇ യുഇAC 110V / AC 220V
ഗ്രേഡ്PC grade: able to make and withstand not to break short-circuit current
വിഭാഗം ഉപയോഗിക്കുകഎസി-33ഐബി
ധ്രുവം2 പി / 3 പി / 4 പി
ഭാരം (കിലോ)0.81-
ജീവിതംElectrical: 2000 times; Mechanical: 5000 times
Rated conditional short circuit current50kA
SCPD (fuse)RT16-00-63A പരിചയപ്പെടുത്തുന്നുRT16-00-100A പരിചയപ്പെടുത്തുന്നു
റേറ്റുചെയ്ത പ്രേരണ പ്രതിരോധം8കെ.വി
Control circuit (Input voltage: AC 110V)റേറ്റുചെയ്ത നിയന്ത്രണ വോളിയംtage Us: AC110V, 50Hz; Correct working condition 85%-110% Us
Control circuit (Input voltage: AC 230V)റേറ്റുചെയ്ത നിയന്ത്രണ വോളിയംtage Us: AC230V, 50Hz; Correct working condition 85%-110% Us
നിലവിലെ ആവൃത്തി50/60Hz
Contact transfer time<50മി.സെ
ഓപ്പറേറ്റിംഗ് ട്രാൻസ്ഫർ സമയം<50മി.സെ
Return transfer time<50മി.സെ
Off-time-55°C ~ +40°C
താപനില പരിധിAverage temperature not more than 35°C in 24 hours
Main Technical Parameters for W2R-100

Figure 9: Main Technical Parameters for W2R-100 Series

7. സജ്ജീകരണവും ഇൻസ്റ്റാളേഷനും

7.1 ഘടകം തിരിച്ചറിയൽ

Familiarize yourself with the different parts of the transfer switch before proceeding with installation.

GEYA Mini ATS Wiring Instructions - Part Names

Figure 10: Analysis of Each Part Name (3P Poles)

  • സിഗ്നൽ ടെർമിനൽ: For control signals.
  • Source A Power Inlet Terminal: Connection point for Main Power (Source A).
  • Source A Power Indicator: Indicates status of Source A.
  • Auto/Manual Mode Switch: Selector for operation mode.
  • Source B Power Indicator: Indicates status of Source B.
  • Transfer Handle: Manual override for switching power sources.
  • Source B Power Inlet Terminal: Connection point for Standby Power (Source B).
  • Power Output (Load Port): Connection point for the electrical load.

7.2 വയറിംഗ് ഡയഗ്രം

Follow the wiring diagrams carefully to ensure correct and safe installation. The device supports connection to mains, generator, or photovoltaic systems.

Combination of Photovoltaic and Generator with ATS

ചിത്രം 11: ഉദാample of Photovoltaic and Generator Combination Wiring

GEYA Mini ATS Wiring Diagram

Figure 12: General Wiring Diagram (3P Poles)

Product Wiring Diagram Exampലെസ്

Figure 13: Various Product Wiring Diagram Exampലെസ്

വയറിംഗ് ഘട്ടങ്ങൾ:

  1. Mount the ATS on a DIN rail in a suitable enclosure.
  2. Connect the Main Power (Source A) to the "Source A Power Inlet Terminal" (AR, AS, AT, AN).
  3. Connect the Standby Power (Source B) to the "Source B Power Inlet Terminal" (BR, BS, BT, BN).
  4. Connect the load to the "Power Output (Load Port)".
  5. Ensure all connections are secure and tightened to prevent loose contacts and overheating.
  6. Connect the control lines (Common Neutral line, Common control line, Alternate control line) as per the diagram for automatic operation.

Video: Wiring Example and Operation Demonstration

Video 1: This video demonstrates the wiring process and basic operation of the GEYA ATS (W2R) unit. It shows how to connect power sources and loads, and how the switch responds to power changes.

8. പ്രവർത്തന നിർദ്ദേശങ്ങൾ

The GEYA Mini ATS can operate in both automatic and manual modes.

8.1 ഓട്ടോമാറ്റിക് മോഡ്

  • Set the "Auto/Manual Mode Switch" to ഓട്ടോ.
  • When normal power supply A is working properly, the A (red light) indicator will be on.
  • If normal power supply A becomes abnormal (e.g., power outage, under/over voltage), the A (green light) indicator will go off, and the switch will automatically transfer the load to backup power supply B.
  • When normal power supply A recovers, the switch will automatically transfer the load back to power supply A.

8.2 മാനുവൽ മോഡ്

  • Set the "Auto/Manual Mode Switch" to മാനുവൽ.
  • To select power supply A, manually operate the red transfer handle towards power supply A. The red light for A will turn on.
  • To select power supply B, manually operate the red transfer handle towards power supply B. The red light for B will turn on.
  • In manual mode, the switch will not automatically transfer power.

Video: Automatic/Manual Transfer Switch Operation

Video 2: This video illustrates the functionality of the GEYA Automatic/Manual Transfer Switch (W2R), demonstrating how it switches between power sources.

Video: ATS Usage Demonstration

Video 3: A brief demonstration of the GEYA ATS (W2R) in action, showing the power transfer process.

9. പരിപാലനം

The GEYA Mini ATS is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.

  • വിഷ്വൽ പരിശോധന: Regularly inspect the switch for any signs of physical damage, loose connections, or discoloration due to overheating.
  • ടെർമിനൽ ടൈറ്റ്നെസ്: Periodically check and tighten all terminal screws to ensure good electrical contact.
  • ശുചിത്വം: Keep the switch free from dust, dirt, and moisture. Use a dry, soft cloth for cleaning.
  • പ്രവർത്തനക്ഷമത പരിശോധന: Occasionally test the automatic transfer function by temporarily disconnecting the main power source (if safe to do so) to ensure the switch transfers to the backup source as expected.

10. പ്രശ്‌നപരിഹാരം

If you encounter issues with your GEYA Mini ATS, consider the following troubleshooting steps:

  • No Power Transfer:
    • Check if both power sources (A and B) are active and within the specified voltage range (85-110% of rated voltagഒപ്പം).
    • Ensure the "Auto/Manual Mode Switch" is set to AUTO for automatic operation.
    • Verify all wiring connections are secure and correct according to the wiring diagram.
    • Check if the current is below 5A, which can cause the coil to malfunction.
  • ഇൻഡിക്കേറ്റർ ലൈറ്റുകൾ പ്രവർത്തിക്കുന്നില്ല:
    • Confirm that the corresponding power source is active.
    • Inspect for loose internal connections (requires professional inspection).
  • അമിത ചൂടാക്കൽ:
    • Ensure the current is not below 5A.
    • അയഞ്ഞ ടെർമിനൽ കണക്ഷനുകൾക്കായി പരിശോധിക്കുക.
    • Verify the load does not exceed the rated current of the switch.

For persistent issues or complex problems, contact qualified electrical personnel or GEYA customer support.

11. വാറൻ്റിയും പിന്തുണയും

GEYA products are manufactured to high-quality standards. For warranty information and technical support, please refer to the official GEYA webനിങ്ങളുടെ സൈറ്റിൽ ബന്ധപ്പെടുക അല്ലെങ്കിൽ നിങ്ങളുടെ പ്രാദേശിക വിതരണക്കാരനെ ബന്ധപ്പെടുക. വാറന്റി ക്ലെയിമുകൾക്കായി നിങ്ങളുടെ വാങ്ങൽ രസീത് സൂക്ഷിക്കുക.