EARU EAL-18 Residual Current Circuit Breaker (RCCB) Instruction Manual

Model: EAL-18 | Brand: EARU

1. ആമുഖം

The EARU EAL-18 Residual Current Circuit Breaker (RCCB) is designed to provide essential leakage protection in electrical circuits. This device is suitable for AC 50Hz systems with rated voltages of 2P 230V or 4P 400V and rated currents ranging from 1A to 63A. Its primary function is to quickly disconnect the power supply in the event of an electric shock or when the grid leakage current exceeds a specified safe value, thereby protecting both personnel and electrical equipment. The EAL-18 is a Type AC RCCB, specifically engineered to detect and respond to power frequency sinusoidal leakage currents, including those that are suddenly applied or slowly rising. It also supports infrequent switching and starting functions for the line. This product complies with the IEC/EN61008-1 standard.

2 സുരക്ഷാ വിവരങ്ങൾ

Please read and understand all safety instructions before installing, operating, or maintaining this device. Failure to follow these instructions may result in serious injury or property damage.

  • ഇൻസ്റ്റാളേഷനും അറ്റകുറ്റപ്പണിയും യോഗ്യതയുള്ള ഇലക്ട്രീഷ്യൻമാർ മാത്രമേ നടത്താവൂ.
  • Always disconnect power before working on electrical circuits.
  • Ensure the device's specifications (voltage, current, sensitivity) match your electrical system requirements.
  • ഉപകരണം കേടായതായി തോന്നിയാൽ അത് പ്രവർത്തിപ്പിക്കരുത്.
  • Regularly test the RCCB using the integrated test button to ensure proper functionality.
  • This device provides residual current protection but does not protect against overcurrent (overload or short circuit). Additional overcurrent protection devices (e.g., MCBs) may be required.

3. ഉൽപ്പന്നം കഴിഞ്ഞുview

3.1 പ്രധാന സവിശേഷതകൾ

  • Type AC RCCB: Designed for power frequency sinusoidal leakage current.
  • ചോർച്ച സംരക്ഷണം: Protects against electric shock and earth leakage faults.
  • Anti-Electromagnetic Interference: Enhanced stability in various environments.
  • ജ്വാല പ്രതിരോധക വസ്തു: Constructed from materials that resist combustion.
  • പാലിക്കൽ: Meets IEC/EN61008-1 standards.
  • Bilateral Busbar Wiring: Offers flexible wiring options.
  • High Connecting Ability: Maximum connecting ability of 35mm² with a wiring torque of 3.5N*m.

3.2 ഘടകങ്ങൾ

Labeled components of the EARU EAL-18 RCCB, showing insulated terminal block, test button, brand logo, leakage tripping indicator window, widening the handle, and wiring diagram.
Figure 1: Labeled Components of the EAL-18 RCCB

This image displays the key parts of the RCCB: the insulated terminal block for secure wiring, the test button for verifying functionality, the EARU brand logo, a window indicating leakage tripping, and a widened handle for easier operation. A basic wiring diagram is also visible.

  • Insulated Terminal Block: For secure and safe electrical connections.
  • ടെസ്റ്റ് ബട്ടൺ: Used for manual testing of the leakage protection function.
  • ബ്രാൻഡ് ലോഗോ: "EARU" and model "EAL-18".
  • Leakage Tripping Indicator Window: Visually indicates when the device has tripped due to a leakage current.
  • കൈകാര്യം ചെയ്യുക: For switching the device ON/OFF and resetting after a trip.
  • വയറിംഗ് ഡയഗ്രം: Printed on the device for correct installation.

4 സ്പെസിഫിക്കേഷനുകൾ

Dimensions and product parameters for EARU EAL-18 RCCB, showing 2P and 4P models.
Figure 2: EAL-18 RCCB Dimensions and Product Parameters

This image provides physical dimensions and a summary of key product parameters for the EAL-18 RCCB, including pole configuration, frequency, breaking capacity, and rated voltage.

Table showing Detection Waveform Type and Classification, and Connection table for Rated Current to Nominal Section Area of Copper Wire.
Figure 3: Detection Waveform Types and Connection Wire Sizes

This image details the types of leakage current waveforms the device can detect (AC Type) and provides a table for recommended nominal section areas of copper wire based on rated current.

Technical Data table for EARU EAL-18 RCCB, detailing electrical features, installation, and environmental conditions.
Figure 4: EAL-18 RCCB Technical Data

This image presents a comprehensive table of technical specifications, including rated current, poles, voltage, frequency, sensitivity, breaking capacity, installation details, and environmental operating conditions.

പട്ടിക 1: പൊതുവായ സവിശേഷതകൾ
ആട്രിബ്യൂട്ട്മൂല്യം
മോഡൽ നമ്പർEAL-18 (RCCB)
ടൈപ്പ് ചെയ്യുകResidual Current (RCD)
റേറ്റുചെയ്ത വോളിയംtage2P 230V / 4P 400V
റേറ്റുചെയ്ത ഫ്രീക്വൻസി50/60Hz
റേറ്റ് ചെയ്ത നിലവിലെ ഓപ്ഷനുകൾ6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
ധ്രുവങ്ങൾ2P, 4P
റേറ്റുചെയ്ത സംവേദനക്ഷമത10mA, 30mA, 100mA, 300mA
ബ്രേക്കിംഗ് കപ്പാസിറ്റി6KA (Icn=Iac=6000A)
സ്റ്റാൻഡേർഡ്IEC61008-1
മൗണ്ടിംഗ്35mm Din Rail
ഇൻസുലേഷൻ വോളിയംtage500V
Dielectric Test Voltage2.5kV for 1 min
Electrical & Mechanical Life4000 സൈക്കിളുകൾ
സംരക്ഷണ ബിരുദംIP20
ആംബിയൻ്റ് താപനില-5°C to +40°C (with daily average ≤35°C)
സംഭരണ ​​താപനില-25°C മുതൽ +70°C വരെ
Terminal Connection Typeകേബിൾ/യു-ടൈപ്പ് ബസ്ബാർ/പിൻ-ടൈപ്പ് ബസ്ബാർ
Terminal Size Top/Bottom for Cable35mm² (18-3)
മുറുകുന്ന ടോർക്ക്3.5 N·m

5. സജ്ജീകരണവും ഇൻസ്റ്റാളേഷനും

The EAL-18 RCCB is designed for mounting on a 35mm DIN rail. Ensure all connections are secure and comply with local electrical codes.

5.1 മൗണ്ടിംഗ്

  1. Ensure the main power supply is OFF before installation.
  2. Attach the RCCB to a standard 35mm DIN rail using its fast clip device.
  3. Verify that the device is securely fastened and cannot move.
Close-up of the EARU EAL-18 RCCB mounted on a DIN rail, showing the secure clip mechanism.
ചിത്രം 5: DIN റെയിൽ മൗണ്ടിംഗ്

This image illustrates how the RCCB is securely mounted onto a standard DIN rail, highlighting the integrated clip for easy installation and removal.

5.2 വയറിംഗ് കണക്ഷനുകൾ

Connect the incoming and outgoing wires to the insulated terminal blocks. The connection can be made from the top or bottom.

  • Use copper wires with a nominal section area appropriate for the rated current (refer to Table 2 below).
  • Ensure all connections are tight with a wiring torque of 3.5 N·m.
  • The device supports Cable, U-type busbar, and Pin-type busbar connections.
Two EARU EAL-18 RCCBs, one 2P and one 4P, showing their front panels with wiring diagrams.
Figure 6: 2P and 4P RCCB Wiring Diagrams

This image displays both the 2-pole (2P) and 4-pole (4P) versions of the EAL-18 RCCB, with their respective wiring diagrams clearly visible on the front panel. The 2P model shows connections for N and L, while the 4P model shows connections for N, 1, 3, 5 and N, 2, 4, 6.

Table 2: Recommended Copper Wire Sizes
റേറ്റുചെയ്ത കറൻ്റ്Nominal Section Area of Copper Wire (mm²)
1~6എ1
10എ1.5
16, 20 എ2.5
25എ4
32എ6
40, 50 എ10
63എ16
80എ25
100എ35

6. ഓപ്പറേഷൻ

6.1 സ്വിച്ച് ഓൺ/ഓഫ്

  • To turn the power ON, push the handle upwards to the 'I-ON' position.
  • To turn the power OFF, push the handle downwards to the 'O-OFF' position.

6.2 Testing the RCCB

It is crucial to regularly test the RCCB to ensure its proper functioning. A monthly test is recommended.

  1. Ensure the RCCB is in the 'I-ON' position.
  2. Press the blue 'TEST' button. The RCCB should immediately trip to the 'O-OFF' position.
  3. If the RCCB does not trip, it may be faulty and should be replaced immediately by a qualified electrician.
  4. To reset the RCCB after a test or trip, push the handle fully downwards to 'O-OFF' and then upwards to 'I-ON'.
Video 1: RCCB Test Function Demonstration

This video demonstrates the operation of the RCCB, including how to switch it on and off, and how to perform the crucial test function using the test button. It shows the device tripping when the test button is pressed, confirming its leakage protection capability.

7. പരിപാലനം

The EAL-18 RCCB requires minimal maintenance. Regular checks are essential to ensure continued safety and performance.

  • പ്രതിമാസ പരിശോധന: As described in Section 6.2, press the test button monthly to verify the tripping mechanism.
  • വിഷ്വൽ പരിശോധന: ഭൗതികമായ കേടുപാടുകൾ, നിറവ്യത്യാസം, അല്ലെങ്കിൽ അയഞ്ഞ കണക്ഷനുകൾ എന്നിവയുടെ ലക്ഷണങ്ങൾക്കായി ഉപകരണം ഇടയ്ക്കിടെ പരിശോധിക്കുക.
  • വൃത്തിയാക്കൽ: ആവശ്യമെങ്കിൽ, ഉണങ്ങിയതും മൃദുവായതുമായ തുണി ഉപയോഗിച്ച് ഉപകരണത്തിന്റെ പുറംഭാഗം സൌമ്യമായി വൃത്തിയാക്കുക. അബ്രസീവ് ക്ലീനറുകളോ ലായകങ്ങളോ ഉപയോഗിക്കരുത്.
  • പ്രൊഫഷണൽ പരിശോധന: It is recommended to have a qualified electrician inspect your electrical system, including RCCBs, periodically.

8. പ്രശ്‌നപരിഹാരം

This section addresses common issues you might encounter with your RCCB.

പട്ടിക 3: ട്രബിൾഷൂട്ടിംഗ് ഗൈഡ്
പ്രശ്നംസാധ്യമായ കാരണംപരിഹാരം
RCCB trips frequently without apparent reason.
  • Actual earth leakage fault in the circuit.
  • സർക്യൂട്ടുമായി ബന്ധിപ്പിച്ചിരിക്കുന്ന തെറ്റായ ഉപകരണം.
  • Moisture or dampness affecting wiring.
  • Overload (though RCCB has no overcurrent protection, an external MCB should trip first).
  • Faulty RCCB.
  • Disconnect all appliances and try to reset. Reconnect one by one to identify the faulty appliance.
  • Inspect wiring for damage or moisture.
  • If the problem persists, consult a qualified electrician to check for hidden leakage faults or a faulty RCCB.
RCCB does not trip when test button is pressed.
  • Faulty RCCB.
  • No power to the RCCB.
  • Ensure power is supplied to the RCCB.
  • If power is present and it still doesn't trip, the RCCB is faulty and must be replaced immediately by a qualified electrician.
RCCB cannot be reset after tripping.
  • Persistent earth leakage fault.
  • Internal damage to the RCCB.
  • Ensure the handle is pushed fully downwards to 'O-OFF' before attempting to push it upwards to 'I-ON'.
  • If a fault is still present, the RCCB will not reset. Identify and rectify the leakage fault.
  • If no fault is found and it still won't reset, the RCCB may be damaged and needs replacement.

9 ഉപയോക്തൃ നുറുങ്ങുകൾ

  • Bipolar Configuration: The EAL-18 is available in both 2-pole (bipolar) and 4-pole configurations, allowing for flexibility in various single-phase and three-phase applications. Ensure you select the correct pole configuration for your specific electrical system.
  • Complementary Protection: Remember that this RCCB provides residual current protection but does not offer overcurrent protection. For comprehensive circuit protection, it should be installed in conjunction with Miniature Circuit Breakers (MCBs) or other appropriate overcurrent protective devices.

10. വാറൻ്റിയും പിന്തുണയും

For warranty information, technical support, or service inquiries, please refer to the seller's specific terms and conditions or contact the point of purchase. Keep your purchase receipt as proof of purchase.


EARU EAL-18 Residual Current Circuit Breaker (RCCB) Functionality Test

EARU EAL-18 Residual Current Circuit Breaker (RCCB) Functionality Test

0:22 • 1280×720 • ഡെമോൺസ്ട്രേഷൻ

അനുബന്ധ രേഖകൾ - EAL-18

പ്രീview EARU EAL-2 Din Rail Circuit Breaker Instruction Manual
Instruction manual for the EARU EAL-2 series din rail circuit breaker, detailing its features, safety instructions, and product parameters for AC 2P 230V 4P 400V A Type RCBO RCCB MCB electronic residual current circuit breakers.
പ്രീview EARU EAPDX-40/63 Series Adjustable Voltagഇ & കറന്റ് പ്രൊട്ടക്ടർ ഉപയോക്തൃ മാനുവൽ
User manual for the EARU EAPDX-40/63 Series Adjustable Voltage & Current Protector, detailing specifications, features, and operation for electrical protection. Includes setup instructions and parameter configuration.
പ്രീview EARU ഇAMPDW-TY-63 സീരീസ് വൈഫൈ സ്മാർട്ട് എനർജി പ്രൊട്ടക്ടർ യൂസർ മാനുവൽ | വാല്യംtage, കറന്റ്, ചോർച്ച സംരക്ഷണം
EARU E-യ്‌ക്കുള്ള സമഗ്രമായ ഉപയോക്തൃ മാനുവൽAMPDW-TY-63 സീരീസ് വൈഫൈ സ്മാർട്ട് എനർജി പ്രൊട്ടക്ടർ. വോളിയത്തിനായുള്ള ഇൻസ്റ്റാളേഷൻ, സവിശേഷതകൾ, സാങ്കേതിക സവിശേഷതകൾ, ആപ്പ് നിയന്ത്രണം, ട്രബിൾഷൂട്ടിംഗ് എന്നിവയെക്കുറിച്ച് അറിയുക.tagഇ, കറന്റ്, ചോർച്ച സംരക്ഷണം.
പ്രീview EARU-X6/8 Metal LED Indicator Light Instruction Manual
User manual for EARU-X6/8 series Metal LED Indicator Lights, detailing safety instructions, warnings, and product description for reliable status indication in industrial and traffic applications.
പ്രീview EARU ഇAMPDW-TY-63 സീരീസ് വൈഫൈ സ്മാർട്ട് എനർജി പ്രൊട്ടക്ടർ യൂസർ മാനുവൽ
EARU E-യ്‌ക്കുള്ള സമഗ്രമായ ഉപയോക്തൃ മാനുവൽAMPDW-TY-63 series WiFi Smart Energy Protector, detailing features, installation, app connection, parameter settings, and troubleshooting. Covers over/under voltage, over current, leakage protection, energy monitoring, and remote control.
പ്രീview EARU D52-2066 Series Single Phase Multi-functional Energy Meter | Technical Specifications
Detailed technical specifications and wiring instructions for the EARU D52-2066 Series DIN-rail single-phase multi-functional energy meter, measuring AC voltage, current, active power, power factor, frequency, and electric energy.