1. ആമുഖം
The Acrel ADL400 three-phase electric meter is designed for precise energy measurement in low voltage systems. This meter complies with the technical requirements of electronic meters as specified in the IEC62053-21 and IEC62053-22 standards. It offers comprehensive monitoring of electrical parameters, making it suitable for various applications requiring accurate power consumption data.
2. സവിശേഷതകൾ
- അളവ്: 3-phase AC kWh, kVarh, U, I, P, Q, S, PF, F, and harmonics (2~31st and total harmonic).
- കൃത്യത: 0.5% (kWh).
- ആവൃത്തി: 45~65Hz.
- റേറ്റുചെയ്ത വോളിയംtage: 3x380~456Vac L-L (direct connect); 3x100~120Vac L-L (via PTs).
- റേറ്റുചെയ്ത നിലവിലെ: 3x10(80)A AC (direct connect); 3x1(6)A AC (via CTs).
- ആശയവിനിമയം: RS485 (MODBUS-RTU).
- ഡിസ്പ്ലേ: 12-bit section LCD with backlight.
- HMI: Keypads for programming.
- Data Function: Data frozen, Max Demand.
- Optional Multi-tariff: 4 Time zones, 2 time interval lists, 14 time intervals per day, and 4 tariff rates (Spike, Peak, Flat, Valley).
- സർട്ടിഫിക്കേഷനുകൾ: IEC, CE, CE-MID, EAC.
3 സ്പെസിഫിക്കേഷനുകൾ
| വിഭാഗം | പരാമീറ്റർ | മൂല്യം |
|---|---|---|
| ജനറൽ | സ്പെസിഫിക്കേഷൻ | 3 ഫേസ് 3 വയറുകൾ, 3 ഫേസ് 4 വയറുകൾ |
| വാല്യംtagഇ അളവ് | റഫറൻസ് വാല്യംtage | 3×100V/3×380Vac, 3×57.7/100Vac, 3×220/380Vac (Can normally work under 1.2 times of rated voltage) |
| ഉപഭോഗം | <10VA (സിംഗിൾ ഫേസ്) | |
| പ്രതിരോധം | >2MΩ | |
| കൃത്യത ക്ലാസ് | Error ±0.2% | |
| നിലവിലെ അളവ് | ഇൻപുട്ട് കറൻ്റ് | 3×1(6)A, 3×10(80)A |
| ഉപഭോഗം | <1VA സിംഗിൾ ഫേസ് റേറ്റഡ് കറൻ്റ് | |
| കൃത്യത ക്ലാസ് | Error ±0.2% | |
| പവർ അളക്കൽ | Active, Reactive, Apparent Power | Error ±0.5% |
| ആവൃത്തി | പരിധി | 45~65Hz, Error ±0.2% |
| മീറ്ററിംഗ് | ഊർജ്ജം | Active energy (Accuracy class: 0.5), Reactive energy (Accuracy class 2) |
| ക്ലോക്ക് | ≤0.5സെ/ഡി | |
| ഡിജിറ്റൽ സിഗ്നൽ | എനർജി പൾസ് ഔട്ട്പുട്ട് | 1 സജീവ ഫോട്ടോകപ്ലർ ഔട്ട്പുട്ട് |
| പൾസ് | Width of Pulse | 80 ± 20 മി |
| സ്ഥിരമായ പൾസ് | 400imp/kWh, 10000imp/kWh (Corresponds with the basic current) | |
| ആശയവിനിമയം | Interface and Protocol | RS485: മോഡ്ബസ് RTU |
| ബൗഡ് നിരക്ക് | 1200bps~19200bps | |
| പരിസ്ഥിതി | പ്രവർത്തന താപനില | -25℃~+55℃ |
| ആപേക്ഷിക ആർദ്രത | ≤95% (കണ്ടൻസേഷൻ ഇല്ല) | |
| അളവുകൾ | മൊത്തത്തിലുള്ള അളവുകൾ | 72*90*65എംഎം |
| ബാറ്ററി ഉൾപ്പെടുത്തിയിട്ടുണ്ട് | അതെ |
4. സജ്ജീകരണം (ഇൻസ്റ്റലേഷൻ)
The ADL400 meter is designed for 35mm DIN rail installation. Ensure all power is disconnected before proceeding with installation.
4.1 മെക്കാനിക്കൽ ഇൻസ്റ്റലേഷൻ
- Push off the buckle on the back side of the meter.
- Install the meter onto a 35mm DIN rail by aligning the slot behind the meter with the rail.
- Buckle up to fix the meter securely on the DIN rail.
- Ensure the meter is successfully installed and stable.
4.2 ഇലക്ട്രിക്കൽ വയറിംഗ്
Refer to the following diagrams for correct wiring based on your system type (Direct Connect or CT Operated).
4.2.1 Direct Connect Type
This section applies to meters with direct current input (e.g., Max 80A Input).
4.2.2 CT Operated Type
This section applies to meters with current transformer (CT) input (e.g., Max 6A Input).
5. പ്രവർത്തന നിർദ്ദേശങ്ങൾ
The ADL400 meter features an LCD display and three buttons for navigation and programming.
5.1 ബട്ടൺ പ്രവർത്തനങ്ങൾ
| ബട്ടൺ ഐക്കൺ | ഫംഗ്ഷൻ | വിവരണം |
|---|---|---|
![]() |
വാല്യംtagഇ, കറന്റ്, മുകളിലേക്ക് | വോളിയം പരിശോധിക്കുകtage and current. Move leftward and change flash in programming menu. |
![]() |
വൈദ്യുതി മുടക്കം | Check the power. Move rightward and change the value on flash. |
![]() |
ഊർജ്ജം, പ്രവേശിക്കുക | Check the energy. Enter/exit programming menu. Save changes. |
5.2 പ്രോഗ്രാമിംഗും കോൺഫിഗറേഷനും
To enter the programming page, long press the 'Enter' button. Use the 'Up' and 'Down' keys to enter the password. Once in the edit page, you can set various parameters.
Key configurable parameters include:
- PT or CT ratio
- Wiring methods (3P4W or 3P3W)
- Real-time clock adjustment
- RS485 (MODBUS-RTU) communication settings (address, baud rate)
After setting all parameters, press the 'Enter' key to save the changes.
5.3 Multi-Tariff Functionality
The ADL400 supports advanced multi-tariff functions, allowing for flexible energy billing based on time of use:
- സമയ മേഖലകൾ: Up to 4 distinct time zones.
- Tariff Rates: Supports 4 tariff rates: Spike, Peak, Flat, and Valley.
- കാലയളവുകൾ: Configurable with 2 time interval lists and up to 14 time intervals per day.
- Data Frozen: Stores frozen data for the last 48 months or last 90 days.
- Max Demand: Records maximum demand and its occurrence time.
6. പരിപാലനം
The Acrel ADL400 meter is designed for reliable operation with minimal maintenance. However, regular checks can ensure optimal performance and longevity.
- വൃത്തിയാക്കൽ: Keep the meter clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
- പരിസ്ഥിതി വ്യവസ്ഥകൾ: Ensure the operating environment remains within the specified temperature (-25℃~+55℃) and humidity (≤95% RH, non-condensing) ranges.
- കണക്ഷൻ സമഗ്രത: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to inaccurate readings or operational issues.
- ഫേംവെയർ അപ്ഡേറ്റുകൾ: നിർമ്മാതാവ് പരിശോധിക്കുക webപ്രകടനം മെച്ചപ്പെടുത്തുന്നതോ പുതിയ സവിശേഷതകൾ ചേർക്കുന്നതോ ആയ ലഭ്യമായ ഏതെങ്കിലും ഫേംവെയർ അപ്ഡേറ്റുകൾക്കായുള്ള സൈറ്റ്.
7. പ്രശ്നപരിഹാരം
This section addresses common issues you might encounter with your ADL400 meter.
7.1 പൊതുവായ പ്രശ്നങ്ങളും പരിഹാരങ്ങളും
-
Q: After the meter is powered on, the power or energy count is inaccurate.
A: Switch the meter display to the power (active power P, power factor λ) interface, and check whether the power display is negative or not. Also, verify if the power factor is between 0.9-0.95. Then, check whether the incoming and outgoing wires of the current signal wire are connected reversely (the incoming wire must be the same as the incoming wire end of the instrument) and consistent with the wiring diagram on the instrument.
-
Q: The instrument cannot communicate with the host computer normally after power on.
A: 1. The voltage value between the communication output A and B of the measuring instrument should be between +(4.4-4.5)V. 2. Check whether the communication wiring method is correctly wired in accordance with the wiring diagram requirements (that is, the communication terminal A/B of the corresponding to communication serial port A/B).
8 ഉപയോക്തൃ നുറുങ്ങുകൾ
- ഘട്ടം കോൺഫിഗറേഷൻ: The meter supports both 3-phase 3-wire and 3-phase 4-wire configurations. Ensure your wiring matches the meter's settings for accurate readings.
- CT Direction: When using Current Transformers (CTs), pay close attention to the current direction indicated by arrows on the CTs and ensure they are installed correctly relative to the meter's input terminals. Incorrect CT orientation is a common cause of inaccurate power readings.
- RS485 ആശയവിനിമയം: For reliable RS485 communication, use a shielded twisted-pair cable (e.g., RVSP 2x1.5mm²) and ensure proper termination if necessary, especially over longer distances or in noisy environments.
- പാസ്വേഡ് സംരക്ഷണം: Utilize the programming password feature to prevent unauthorized changes to the meter's configuration.
9. വാറൻ്റിയും പിന്തുണയും
The Acrel ADL400 MID 3 Phase Energy Meter comes with a 2 വർഷത്തെ വാറൻ്റി വാങ്ങിയ തീയതി മുതൽ. സാധാരണ ഉപയോഗത്തിലുള്ള മെറ്റീരിയലുകളിലെയും വർക്ക്മാൻഷിപ്പുകളിലെയും വൈകല്യങ്ങൾ ഈ വാറന്റി ഉൾക്കൊള്ളുന്നു.
For technical support, troubleshooting assistance, or warranty claims, please contact Acrel Official Store customer service. Ensure you have your product model number and purchase details ready.
10. അപേക്ഷകൾ
The ADL400 meter is versatile and can be applied in various settings for energy monitoring and management:
- വ്യാവസായിക: Mining, Petrochemical, Factories.
- വാണിജ്യം: Buildings, Hotel Apartments, Hospitals.
- അടിസ്ഥാന സൗകര്യങ്ങൾ: Municipal Engineering, Transportation.
- പ്രത്യേകം: EV Chargers, Solar PV installations, Electrical Safety monitoring.
11. സർട്ടിഫിക്കേഷനുകൾ
The Acrel ADL400 meter holds the following important certifications, ensuring its quality and compliance with international standards:
- CE
- CE-MID
- എഅച്
- IEC62053-21
- IEC62053-22