AKR-logo

AKR F-102 Temperature Controller Panel

AKR-F-102-Temperature-Controller-Panel-product

F-102 Temperature Controller Panel Specifications

  1. അളവുകൾ: 150 x 56 x 18 മിമി
  2. Set Temp Range: 15°C~35°C (59°F~95°F)
  3. Timer Range: 1~24 hours (Display hidden when set to 0 hour)
  4. Infrared Effective Range: 6~8 meters (May vary slightly depending on environment)
  5. Function Selection: COOL (Cooling), HEAT (Heating), FAN (Ventilation)
  6. °C/°F Switching:
    • Via remote control or Hold both Temp +/- buttons simultaneously for 10 seconds after power-on
  7. Cooling Only / Heat-Cool (Low current, High current, 25A)
  8. Wireless Connection: Between control box and remote

F-102 Wireless Remote Controller / Receiver & Control Box

  • Remote Controller: 150 x 56 x 18 mm
  • Controller Dock: 76 x 63 x 23 mm
  • നിയന്ത്രണ ബോക്സ്: 130 x 70 x 50 മിമി

AKR-F-102-Temperature-Controller-Panel-

F-102 Remote Control Operation Manual

New Battery Installation (RESET State)
When batteries are installed for the first time, all LCD segments will illuminate for 5 seconds to verify display functionality.

സ്ഥിര ക്രമീകരണങ്ങൾ:

  1. Operation Mode → COOL
  2. Set Temperature → 28°C
  3. Fan Speed → AUTO
  4. Sleep Function → OFF
  5. Airflow Direction → Not available (for chiller unit models)
  6. Timer Function → Disabled (0 hour)

ഓപ്പറേഷൻ മോഡ് തിരഞ്ഞെടുക്കൽ

  • Press the “Mode” button to cycle through: COOL (Cooling) → FAN (Ventilation) → HEAT (Heating)

Temperature Setting (SET TEMP)

  1. In COOL mode: Press ▲/▼ to adjust temperature (15°C~35°C).
  2. In HEAT mode: Press ▲/▼ to adjust temperature (15°C~35°C).
  3. In FAN mode: Temperature setting is disabled.

ഫാൻ സ്പീഡ് ക്രമീകരണം

  • Press the “Fan Speed” button to cycle through: HIGH → MED (Medium) → LOW → AUTO

Sleep Function (SLEEP)

  1. For use during sleep
  2. Effective in COOL mode only:
    • സജീവമാക്കിയ ശേഷം
    • Temperature increases by 1°C after 1 hour
    • Increases another 1°C after 2 hours (total +2°C)
    • No further adjustment afterward
    • Returns to original set temperature after 8 hours
  3. Press again to cancel SLEEP function

Airflow Direction (OSC.)
Not available (for chiller unit models)

Auto-OFF Timer Setting (TIMER) While unit is ON
Press “Timer” button (▲/▼) to set desired shutdown time

Auto-ON Timer Setting (TIMER) While unit is OFF
Press “Timer” button (▲/▼) to set desired startup time

പവർ ഓൺ/ഓഫ്

  • Press “POWER ON/OFF” button to toggle system power

റിസീവർ LED ഇൻഡിക്കേറ്റർ സ്റ്റാറ്റസ്

  1. Power-on Confirmation → Blue and orange LEDs flash simultaneously once
  2. Blue LED Steady On → Water valve ON during operation
  3. Blue LED Slow Flash → Water valve OFF during operation (serves as power indicator)
  4. Blue LED Rapid Flash → Abnormal system status
  5. Green LED On → Comfort Sleep mode active
  6. Red LED On → Scheduled ON/OFF timer active
  7. Orange LED On → Sleep mode + scheduled OFF timer active
  8. Remote Signal Reception → Buzzer emits one short beep

Air Conditioning Functions

കൂളിംഗ് മോഡ്

 Valve Contact Operation

  1. Valve contact opens when:
    • Room temperature ≥ (Set temperature + 0.5°C)
  2. Valve contact closes when:
    • Room temperature ≤ (Set temperature – 0.5°C)

ഫാൻ സ്പീഡ് ക്രമീകരണങ്ങൾ

  • AUTO (Automatic) → HIGH (High speed)
  • MED (Medium speed) → LOW (Low speed)

ഓട്ടോ ഫാൻ വേഗത
മൂന്ന്-എസ്tage auto fan speed logic in cooling mode

Δ = (Room – Set temp) ഫാൻ വേഗത
Δ ≥ 3.0 ഉയർന്നത്
2.5 ≤ Δ ≥ 2.0 Maintain Current Speed
Δ = 1.5 ഇടത്തരം
1.0 ≥ Δ ≥ 0.5 Maintain Current Speed
Δ ≤ 0 താഴ്ന്നത്

പ്രധാന യൂണിറ്റ്
ON, Heater: OFF

ചൂടാക്കൽ മോഡ്

2-Pipe/DX Valve Operation

  1. Valve contact opens when Set temp ≥ (Room temp + 0.5°C).
  2. Valve contact closes when Set temp ≤ (Room temp – 0.5°C).
  3. Heater contact ON, Main unit contact ON.

4-Pipe/Electric Heater Operation

  1. Heater contact opens when Set temp ≥ (Room temp + 0.5°C).
  2. Heater contact closes when Set temp ≤ (Room temp – 0.5°C).
  3. Valve contact OFF, Main unit contact ON.
  4. Fan delay: After shutdown in heating mode, low-speed contact delays 30 sec before closing.

 Selectable Fan Speed

  • Auto → High → Medium → Low

1 Auto Fan Speed
3-സെtage auto speed logic for heating mode

Δ = (Room – Set temp) ഫാൻ വേഗത
Δ ≥ 3.0 ഉയർന്നത്
2.5 ≤ Δ ≥ 2.0 Maintain Current Speed
Δ = 1.5 ഇടത്തരം
1.0 ≥ Δ ≥ 0.5 Maintain Current Speed
Δ ≤ 0 താഴ്ന്നത്

വിപുലീകൃത മോഡലുകൾ

Additional Features for DX (Direct Expansion) AC Units

  • 3-minute delay start protection for 3-way valve (optional high-current RELAY for compressor control)
  • OSC. louver setting: Controls main unit RELAY → ON/OFF for louver function

Jumper Setting Table

പരാമീറ്റർ സ്ഥാനം സ്ഥിരസ്ഥിതി ക്രമീകരണ ശ്രേണി
1 : Power-on Behavior SW1:5&4 Jumper പവർ ഓഫ് SW1:5=Short, SW1:4=Short (Power-off)
* SW1:5=Open, SW1:4=Short (Power-off)
SW1:5=Short, SW1:4=Open (Power-on)
SW1:5=Open, SW1:4=Open (Memory)
2:  Valve (3-way/Compressor) Delay Protection SW1:3 Jumper കാലതാമസം ഇല്ല * SW1:3=Short (No Delay)
SW1:3=Open (3 min)
3 : Coil Configuration SW1:2 Jumper 2-Pipe/DX * SW1:2=Short (2-Pipe/DX)
SW1:2=Open (4-Pipe/Electric)
4 : Unit Interlock/ Louver Contact Function SW1:1 Jumper Unit Interlock * SW1:1=Short (Unit Interlock)
SW1:1=Open (Louver Function)

കുറിപ്പ്

  1. Configure jumper settings by cutting (Open) or connecting (Short) the corresponding SW1 jumpers on the control box.
  2. For louver (air direction) function [DX model]: Set SW1:1 to Open. The unit interlock contact will be converted to louver contact output (dry contact).
  3. * indicates factory default setting.

പതിവുചോദ്യങ്ങൾ

താപനില ക്രമീകരണം എങ്ങനെ മാറ്റാം?

Use the remote controller to adjust the temperature by pressing the Temp +/- buttons or via the temperature settings on the control box.

പ്രമാണങ്ങൾ / വിഭവങ്ങൾ

AKR F-102 Temperature Controller Panel [pdf] നിർദ്ദേശ മാനുവൽ
F-102, JohnPoint, F-102 Temperature Controller Panel, F-102, Temperature Controller Panel, Controller Panel, Panel

റഫറൻസുകൾ

ഒരു അഭിപ്രായം ഇടൂ

നിങ്ങളുടെ ഇമെയിൽ വിലാസം പ്രസിദ്ധീകരിക്കില്ല. ആവശ്യമായ ഫീൽഡുകൾ അടയാളപ്പെടുത്തി *