അപ്പോളോ 1420608

Apollo Valve 14-200 Series Bronze Safety Relief Valve

മോഡൽ: 1420608

1. ആമുഖം

This manual provides essential information for the proper installation, operation, and maintenance of the Apollo Valve 14-200 Series Bronze Safety Relief Valve. This high-capacity steam safety valve is designed to protect heating boiler systems by automatically relieving excess pressure. Adherence to the guidelines presented herein is crucial for ensuring the safety, longevity, and optimal performance of the valve.

The Apollo Valve 14-200 series is ASME safety rated for Section IV heating boilers, making it suitable for use with medium and large size commercial and industrial heating boilers.

2 സുരക്ഷാ വിവരങ്ങൾ

മുന്നറിയിപ്പ്: Improper installation, operation, or maintenance of this safety relief valve can result in property damage, serious injury, or death. Always follow all local codes, regulations, and manufacturer instructions.

  • Ensure the valve is installed by qualified personnel in accordance with all applicable codes and standards.
  • Verify that the valve's set pressure (15 psi) is appropriate for the system it is protecting.
  • ടി ചെയ്യരുത്amper with the factory-set pressure. Any adjustments must be performed by authorized personnel using proper calibration equipment.
  • Ensure proper discharge piping is installed to safely vent steam or fluid away from personnel and equipment.
  • Regularly inspect the valve for signs of damage, corrosion, or leakage.
  • Always depressurize the system before attempting any maintenance or inspection.

3. ഉൽപ്പന്നം കഴിഞ്ഞുview

The Apollo Valve 14-200 Series is a robust bronze safety relief valve designed for reliable overpressure protection in steam heating boiler systems. Its construction features a durable cast bronze body, a steel spring, and a PTFE-faced disc for a positive seal.

Apollo Valve 14-200 Series Bronze Safety Relief Valve

എ വിശദമായി view of the Apollo Valve 14-200 Series Bronze Safety Relief Valve, showing its robust bronze body, threaded inlet and outlet connections, and the top-mounted lift lever mechanism. The product label is visible, indicating model and pressure specifications.

പ്രധാന സവിശേഷതകൾ:

  • Relief Pressure: Preset to 15 psi for effective pressure release.
  • ഇൻ‌ലെറ്റ് കണക്ഷൻ: 2-1/2" male NPT threaded inlet for secure connection.
  • ഔട്ട്ലെറ്റ് കണക്ഷൻ: 2-1/2" female NPT outlet.
  • നിർമ്മാണം: Cast bronze body and steel spring for excellent corrosion resistance.
  • സീലിംഗ്: Flat seat with a PTFE-faced disc for a reliable, positive seal.
  • സർട്ടിഫിക്കേഷൻ: ASME safety rated for Section IV heating boilers.
  • ഡ്രെയിനേജ് കണക്ഷൻ: Features a 3/8" NPT side tapping for drain connection.
  • പ്രവർത്തന താപനില: Suitable for operating temperatures up to 250 degrees F.

4. സജ്ജീകരണവും ഇൻസ്റ്റാളേഷനും

Installation of the Apollo Valve 14-200 Series Safety Relief Valve should only be performed by a qualified and licensed professional in accordance with all local and national plumbing and boiler codes.

ഇൻസ്റ്റലേഷൻ ഘട്ടങ്ങൾ:

  1. System Preparation: Ensure the boiler system is depressurized and cooled before beginning installation.
  2. ഇൻ‌ലെറ്റ് കണക്ഷൻ: Thread the 2-1/2" male NPT inlet of the valve into the designated female NPT connection on the boiler. Use appropriate thread sealant to ensure a leak-free connection. Do not overtighten.
  3. ഔട്ട്ലെറ്റ് കണക്ഷൻ: Connect suitable discharge piping to the 2-1/2" female NPT outlet of the valve. The discharge piping must be adequately sized, sloped for drainage, and routed to a safe discharge point where steam or hot water can be safely released without causing harm or damage. Avoid any restrictions or valves in the discharge line.
  4. Drain Connection (Optional): If required, connect a 3/8" NPT drain line to the side tapping for condensate drainage.
  5. അന്തിമ പരിശോധന: After installation, slowly repressurize the system and carefully inspect all connections for leaks.

5. പ്രവർത്തന തത്വങ്ങൾ

The Apollo Valve 14-200 Series Safety Relief Valve operates automatically to protect the boiler from overpressure conditions. It is a spring-loaded, direct-acting valve.

  • Under normal operating conditions, the system pressure is below the valve's set pressure (15 psi), and the valve remains closed, maintaining system integrity.
  • If the system pressure exceeds the 15 psi set point, the force exerted by the pressure on the valve's disc overcomes the spring force, causing the disc to lift and the valve to open.
  • Excess steam or fluid is then discharged through the outlet, reducing the system pressure to a safe level.
  • Once the system pressure drops below the reseating pressure, the spring force closes the valve, restoring normal operation.
  • The valve also features a manual lift lever for periodic testing, which should be performed carefully and only when the system is at a safe operating pressure, to ensure the valve is not seized. Consult boiler operation guidelines for proper testing procedures.

6. പരിപാലനം

Regular maintenance is essential to ensure the continued reliability and safety of your Apollo safety relief valve. All maintenance should be performed by qualified personnel.

മെയിൻ്റനൻസ് ഷെഡ്യൂൾ:

  • വാർഷിക പരിശോധന: Visually inspect the valve for any signs of external damage, corrosion, or leaks. Check the discharge piping for obstructions.
  • പ്രവർത്തന പരിശോധന: Periodically test the valve by manually lifting the lever to ensure the disc moves freely and reseats properly. This should be done in accordance with boiler manufacturer recommendations and safety protocols.
  • വൃത്തിയാക്കൽ: If the valve shows signs of weeping or leakage, it may indicate debris on the seat. A gentle manual lift of the lever while the system is under pressure (if safe to do so per boiler manual) can sometimes clear minor debris. If leakage persists, the valve may need to be replaced.
  • മാറ്റിസ്ഥാപിക്കൽ: Safety relief valves have a finite lifespan. It is recommended to replace the valve according to boiler manufacturer guidelines or if it fails any operational tests, shows signs of significant wear, or has discharged frequently.

7. പ്രശ്‌നപരിഹാരം

This section provides basic troubleshooting steps for common issues. For complex problems or if you are unsure, always consult a qualified professional.

പ്രശ്നംസാധ്യമായ കാരണംപരിഹാരം
Valve constantly weeping or leaking
  • വാൽവ് സീറ്റിൽ അവശിഷ്ടങ്ങൾ
  • Damaged seat or disc
  • System pressure too close to set pressure
  • Attempt to clear debris by carefully lifting the lever (if safe)
  • Replace the valve if seat/disc is damaged
  • Verify system operating pressure
Valve fails to open at set pressure
  • Valve seized due to corrosion or deposits
  • Incorrectly installed valve
  • Do NOT attempt to force open. Replace the valve immediately.
  • Verify correct installation by a professional.
Valve opens too frequently
  • System overpressure condition
  • ബോയിലർ തകരാറുകൾ നിയന്ത്രിക്കുന്നു
  • Investigate and resolve the cause of system overpressure.
  • Inspect and repair boiler pressure controls.

8 സ്പെസിഫിക്കേഷനുകൾ

Detailed technical specifications for the Apollo Valve 14-200 Series Bronze Safety Relief Valve.

ആട്രിബ്യൂട്ട്മൂല്യം
മോഡൽ നമ്പർ1420608
ബ്രാൻഡ്അപ്പോളോ
വാൽവ് തരംസുരക്ഷാ ദുരിതാശ്വാസ വാൽവ്
ബോഡി മെറ്റീരിയൽവെങ്കലം
സ്പ്രിംഗ് മെറ്റീരിയൽഉരുക്ക്
Disc MaterialPTFE-faced
സീറ്റ് മെറ്റീരിയൽPTFE-coated EPDM O-ring
സമ്മർദ്ദം സജ്ജമാക്കുക15 psi
ഇൻലെറ്റ് കണക്ഷൻ തരം2-1/2" Male NPT
ഔട്ട്‌ലെറ്റ് കണക്ഷൻ തരം2-1/2" Female NPT
ഡ്രെയിൻ കണക്ഷൻ3/8" NPT Side Tapping
പരമാവധി പ്രവർത്തന താപനില250°F
ASME സർട്ടിഫിക്കേഷൻSection IV Heating Boilers
നിർമ്മാതാവ്Conbraco
യു.പി.സി670750498381
പാക്കേജ് അളവുകൾ9.7 x 7.2 x 6.1 ഇഞ്ച്
ഇനത്തിൻ്റെ ഭാരം12 പൗണ്ട്

9. വാറൻ്റിയും പിന്തുണയും

For specific warranty information regarding the Apollo Valve 14-200 Series Safety Relief Valve, please refer to the documentation provided at the time of purchase or contact Apollo Valves directly. Warranty terms typically cover manufacturing defects under normal use and service.

For technical support, replacement parts, or further inquiries, please contact Apollo Valves customer service. Apollo Valves is a brand of Conbraco, a company founded in 1928 and headquartered in Matthews, NC, meeting international standard ISO/IEC 17025:2005.

നിർമ്മാതാവിനെ ബന്ധപ്പെടുക: Please visit the official Apollo Valves website or consult your local distributor for the most current contact information.

അനുബന്ധ രേഖകൾ - 1420608

പ്രീview അപ്പോളോ എയർ ഇലക്ട്രിക് സ്കൂട്ടർ ഉപയോക്തൃ മാനുവൽ - സജ്ജീകരണം, പ്രവർത്തനം, സുരക്ഷ
അപ്പോളോ എയർ ഇലക്ട്രിക് സ്കൂട്ടറിനായുള്ള സമഗ്രമായ ഉപയോക്തൃ മാനുവൽ, സജ്ജീകരണം, പ്രവർത്തനം, സുരക്ഷാ മാർഗ്ഗനിർദ്ദേശങ്ങൾ, അറ്റകുറ്റപ്പണികൾ, വാറന്റി വിവരങ്ങൾ എന്നിവ ഉൾക്കൊള്ളുന്നു. നിങ്ങളുടെ അപ്പോളോ എയർ എങ്ങനെ സുരക്ഷിതമായി ആസ്വദിക്കാമെന്ന് മനസിലാക്കുക.
പ്രീview പുഷ്-ടു-കണക്റ്റ് വാഷിംഗ് മെഷീൻ ഔട്ട്ലെറ്റ് ബോക്സ് ഇൻസ്റ്റലേഷൻ ഗൈഡ്
അപ്പോളോ പുഷ്-ടു-കണക്റ്റ് വാഷിംഗ് മെഷീൻ ഔട്ട്‌ലെറ്റ് ബോക്‌സിന്റെ ടെക്‌റ്റൈറ്റ് ഇൻസ്റ്റാൾ ചെയ്യുന്നതിനുള്ള നിർദ്ദേശ ഷീറ്റ്, ഘട്ടം ഘട്ടമായുള്ള ഇൻസ്റ്റാളേഷനും വാൽവ് കോൺഫിഗറേഷൻ വിശദാംശങ്ങളും ഉൾപ്പെടെ.
പ്രീview Apollo Tank Max 69TANKMAX Installation Instructions
Detailed installation instructions and safety precautions for the Apollo Tank Max 69TANKMAX thermostatic mixing valve, designed to provide more hot water safely.
പ്രീview അപ്പോളോ ഗോ ഇലക്ട്രിക് സ്കൂട്ടർ യൂസർ മാനുവൽ
അപ്പോളോ ഗോ ഇലക്ട്രിക് സ്കൂട്ടറിനായുള്ള സമഗ്രമായ ഉപയോക്തൃ മാനുവൽ, സജ്ജീകരണം, പ്രവർത്തനം, അറ്റകുറ്റപ്പണികൾ, ട്രബിൾഷൂട്ടിംഗ്, സുരക്ഷാ മാർഗ്ഗനിർദ്ദേശങ്ങൾ എന്നിവ ഉൾക്കൊള്ളുന്നു.
പ്രീview Apollo POWER VS Series Turbine Instruction Manual - HVLP Spraying Guide
Comprehensive instruction manual for the Apollo POWER VS Series HVLP Turbine Spray Systems. Learn about setup, operation, maintenance, and best practices for achieving professional spray finishing results.
പ്രീview അപ്പോളോ ഗോ ഇലക്ട്രിക് സ്കൂട്ടർ യൂസർ മാനുവൽ
അപ്പോളോ ഗോ ഇലക്ട്രിക് സ്കൂട്ടറിനായുള്ള സമഗ്രമായ നിർദ്ദേശങ്ങൾ ഈ ഉപയോക്തൃ മാനുവലിൽ അടങ്ങിയിരിക്കുന്നു, അൺബോക്സിംഗ്, അസംബ്ലി, ഓപ്പറേഷൻ, ചാർജിംഗ്, മെയിന്റനൻസ്, സുരക്ഷാ മാർഗ്ഗനിർദ്ദേശങ്ങൾ, ട്രബിൾഷൂട്ടിംഗ്, വാറന്റി വിവരങ്ങൾ എന്നിവ ഇതിൽ ഉൾപ്പെടുന്നു. നിങ്ങളുടെ അപ്പോളോ ഗോ ഇലക്ട്രിക് സ്കൂട്ടർ എങ്ങനെ സജ്ജീകരിക്കാമെന്നും ഓടിക്കാമെന്നും പരിപാലിക്കാമെന്നും മനസ്സിലാക്കുക.