1. ഉൽപ്പന്നം കഴിഞ്ഞുview
The Danfoss RA2000 Fixed Capacity NPT Radiator Valves are designed to regulate the flow of hot water or low-pressure steam in heating systems. These valves are suitable for use with free-standing radiators, baseboards, or convectors in both hot water and two-pipe steam systems. The design allows for separate packaging of operators and valves, providing flexibility for installers to select the appropriate combination for specific applications. A key feature of the RA2000 valves is the replaceable packing gland assembly, which can be serviced even while the heating system remains operational.

Figure 1: Danfoss RA2000 Fixed Capacity NPT Radiator Valve. This image displays the Danfoss RA2000 Fixed Capacity NPT Radiator Valve. The valve body is metallic, featuring a female pipe thread (FPT) connection on one end and a male pipe thread (MPT) union tailpiece on the other. A brass valve insert with a pushpin mechanism is visible on the side. A separate gray plastic protective cap, used for manual control during installation, is shown next to the valve.
2 പ്രധാന സവിശേഷതകൾ
- Designed for hydronic hot water and low-pressure steam applications.
- Features a replaceable packing gland assembly, allowing for maintenance while the system is operational.
- Equipped with a sturdy EPDM rubber valve disc, ensuring a reliable seal against the valve seat at differential pressures up to 15 PSI in hot water systems and 15 psig for low-pressure steam systems.
- Includes a manual plastic cap for protecting the valve pushpin and enabling manual control during the installation phase.
- Valves are designed to remain normally open when no operator is mounted.
- Conforms to ASHRAE / ANSI Standard 102-1983.
3. അപേക്ഷകൾ
The Danfoss RA2000 valves are suitable for installation in various heating system configurations:
- Free-standing radiators
- ബേസ്ബോർഡുകൾ
- കൺവെക്ടറുകൾ
4. Compatible Operators
The RA2000 valves are designed to work with a range of Danfoss operators. Operators are sold separately to allow for system customization. Compatible operators include:
- AVEO Valve Mount Operators: 015G4290, 015G4292, 015G4240, 015G4042
- RA 2000 Wall Mount Operators: 013G8562, 013G8565, 013G8568, 013G8564
- Other compatible models: 013G5002, 013G1350
5. സജ്ജീകരണവും ഇൻസ്റ്റാളേഷനും
Installation of the Danfoss RA2000 valve should be performed by a qualified professional in accordance with local plumbing and heating codes. The valve is designed for easy integration into existing or new systems.
ഇൻസ്റ്റലേഷൻ ഘട്ടങ്ങൾ:
- Ensure the heating system is depressurized and drained before beginning installation.
- Connect the valve to the radiator or heating element using the appropriate NPT connections. The valve features a female pipe thread (FPT) on one end and a male pipe thread (MPT) union tailpiece on the other for secure attachment.
- During installation, the supplied manual plastic cap can be used to protect the valve pushpin and provide temporary manual control of the valve.
- Once the valve is securely installed, an appropriate Danfoss RA2000 operator (purchased separately) can be mounted onto the valve.
- Refill and repressurize the system, checking for any leaks.
കുറിപ്പ്: The valve remains normally open when no operator is mounted, allowing for initial system filling and purging.
6. ഓപ്പറേഷൻ
The Danfoss RA2000 valve operates by controlling the flow of heating medium to the radiator or convector. When a compatible thermostatic radiator operator is installed, it senses the room temperature and adjusts the valve opening to maintain the desired temperature. Without an operator, the valve will remain in a fully open position, allowing maximum flow.
സ്വമേധയാലുള്ള നിയന്ത്രണം:
The manual plastic cap provided with the valve can be used for temporary manual control during installation or in the absence of an operator. This cap allows for basic open/close functionality by pressing down on the valve pushpin.
7. പരിപാലനം
The Danfoss RA2000 valve is designed for long-term reliability with minimal maintenance. A key maintenance feature is the replaceable packing gland assembly.
Replacing the Packing Gland:
Should the packing gland require replacement, this can be performed while the heating system is still in operation, minimizing downtime and inconvenience. Refer to the specific instructions provided with the replacement packing gland kit for detailed steps. It is recommended that this procedure be carried out by a qualified technician.
8. പ്രശ്നപരിഹാരം
If you experience issues with your Danfoss RA2000 radiator valve, consider the following:
- No Heat/Insufficient Heat: Ensure the thermostatic operator (if installed) is set to the desired temperature. Check if the valve pushpin is free to move. Verify that the system pressure is adequate.
- അമിത ചൂടാക്കൽ: Check the operator setting. Ensure the valve is not stuck in the open position.
- ചോർച്ച: Inspect all connections for proper sealing. If a leak is detected around the valve stem, the packing gland may need to be replaced.
For persistent issues, contact a qualified heating technician or Danfoss customer support.
9 സ്പെസിഫിക്കേഷനുകൾ
| ആട്രിബ്യൂട്ട് | വിശദാംശങ്ങൾ |
|---|---|
| നിർമ്മാതാവ് | ഡാൻഫോസ് |
| Part Number (1" Straight) | DANFOSS:013G8025 |
| ഇനം മോഡൽ നമ്പർ | 013G80XX |
| വലിപ്പം | 1" Straight |
| ഇനത്തിൻ്റെ ഭാരം | 1 പൗണ്ട് |
| ഉൽപ്പന്ന അളവുകൾ (L x W x H) | 5.8 x 4 x 2.5 ഇഞ്ച് |
| നിറം | നിക്കിൾ |
| ഇനത്തിൻ്റെ പാക്കേജ് അളവ് | 1 |
| ഉൾപ്പെടുത്തിയ ഘടകങ്ങൾ | 1x വാൽവ് |
| ബാറ്ററികൾ ആവശ്യമുണ്ടോ? | ഇല്ല |
| ASIN | B079J5J76T |
| ആദ്യ തീയതി ലഭ്യമാണ് | സെപ്റ്റംബർ 11, 2025 |
10. വാറൻ്റിയും പിന്തുണയും
For information regarding product warranty, technical support, or service, please refer to the official Danfoss website or contact Danfoss customer service directly. Ensure you have your product model number (RA2000) and specific part number (e.g., 013G8025) available when seeking support.
Official Danfoss Webസൈറ്റ്: www.danfoss.com