ഉൽപ്പന്നം കഴിഞ്ഞുview
The Diversitech Condensate Cop (Model CC-1) is a specialized clamp-on float switch engineered for installation in HVAC drain pans. Its primary function is to detect rising water levels within the drain pan, signaling a potential overflow condition. Upon detection, the switch activates, typically by opening a normally closed circuit, which can be wired to interrupt the thermostat (compressor) circuit, thereby shutting down the HVAC unit to prevent water damage.
This device features a large over-clamping area, ensuring compatibility with various drain pan types, including formed plastic and galvanized sheet metal. A unique swivel float/probe assembly allows for flexible positioning to accommodate sloped pan sides, optimizing operation. The probe is equipped with an inlet grill to prevent obstruction by insulation or debris, ensuring reliable performance. The internal magnetically actuated switch is sealed for durability and consistent function.

Image: The Diversitech CC-1 Condensate Cop Drain Pan Switch, a red clamp-on device with a yellow wire, designed to detect high water levels in HVAC drain pans.
സുരക്ഷാ വിവരങ്ങൾ
Please read and understand all safety instructions before installing or operating the Diversitech CC-1 Condensate Cop. Failure to follow these instructions may result in property damage, personal injury, or death.
- വൈദ്യുത അപകടം: Always disconnect power to the HVAC unit at the main service panel before performing any installation, maintenance, or troubleshooting.
- യോഗ്യതയുള്ള ഉദ്യോഗസ്ഥർ: Installation and wiring should only be performed by a qualified HVAC technician or electrician in accordance with all local and national electrical codes.
- ഉദ്ദേശിച്ച ഉപയോഗം: This device is designed for use as a high-level float switch in HVAC drain pans. Do not use for applications other than its intended purpose.
- ജലക്ഷാമം തടയൽ: While this switch is designed to help prevent water damage, it is not a substitute for regular maintenance and inspection of the HVAC system's condensate drainage.
- ശരിയായ സ്ഥാനം: Ensure the switch is installed in a location where it can accurately detect rising water levels without being obstructed by debris or insulation.
ബോക്സിൽ എന്താണുള്ളത്
- Diversitech CC-1 Condensate Cop Drain Pan Switch (1 Count)
സ്പെസിഫിക്കേഷനുകൾ
| മോഡൽ നമ്പർ | CC-1 |
| ഉൽപ്പന്ന അളവുകൾ | 6 x 3.2 x 2.5 ഇഞ്ച് |
| ഇനത്തിൻ്റെ ഭാരം | 1.76 ഔൺസ് |
| സ്വിച്ച് തരം | Magnetically Actuated Float Switch (Normally Closed) |
| വൈദ്യുതി ബന്ധം | Two-wire connection for thermostat (compressor) circuit |
| അനുയോജ്യത | Formed plastic and galvanized sheet metal drain pans |
| മാതൃരാജ്യം | യുഎസ്എ |
സജ്ജീകരണവും ഇൻസ്റ്റാളേഷനും
Proper installation is crucial for the reliable operation of the Condensate Cop. Follow these steps carefully:
- വൈദ്യുതി വിച്ഛേദിക്കൽ: Before beginning any work, ensure the power to the HVAC unit is completely disconnected at the circuit breaker or main service panel. Verify with a voltagഇ ടെസ്റ്റർ.
- Identify Drain Pan: Locate the primary drain pan of your HVAC indoor unit. Ensure it is clean and free of debris.
- Positioning the Switch: The Condensate Cop is designed to clamp onto the edge of the drain pan.
- cl സ്ഥാപിക്കുകamp-on mechanism over the edge of the drain pan.
- Position the float/probe assembly within the pan. The assembly swivels, allowing you to adjust its angle to ensure the float is vertical and can move freely, especially with sloped pan sides.
- Ensure the float is positioned at a height that will trigger the switch before water overflows the pan. A common practice is to set it slightly above the normal operating water level, but well below the pan's rim.
- Cl സുരക്ഷിതമാക്കുകamp: cl-യിലെ സ്ക്രൂകൾ ശക്തമാക്കുകamp mechanism to firmly secure the switch to the drain pan. Do not overtighten, but ensure it is stable and will not shift.
- വയറിംഗ് കണക്ഷൻ: The Condensate Cop features a two-wire connection. This switch is normally closed (NC), meaning it completes the circuit when water levels are normal and opens the circuit when water rises to the trip point.
- Typically, this switch is wired in series with the low-voltage thermostat (compressor) circuit (e.g., the "Y" wire).
- Cut the low-voltage wire that controls the compressor (usually the yellow wire from the thermostat to the outdoor unit or control board).
- Connect one wire from the Condensate Cop to one end of the cut wire and the other Condensate Cop wire to the other end of the cut wire. Use appropriate wire nuts or connectors, ensuring secure and insulated connections.
- Consult your HVAC unit's wiring diagram for specific low-voltage control circuit details if unsure.
- ടെസ്റ്റ് ഓപ്പറേഷൻ:
- Carefully restore power to the HVAC unit.
- Manually lift the float on the Condensate Cop to simulate a high water level. The HVAC unit (compressor) should shut off.
- Lower the float. The HVAC unit should resume normal operation after a short delay (if applicable to your system).
- If the unit does not shut off or resume as expected, re-check wiring and float positioning.
ഓപ്പറേഷൻ
The Diversitech CC-1 Condensate Cop operates as a safety device. Under normal conditions, with the drain pan clear of excessive water, the float remains in its low position, and the switch maintains a closed circuit, allowing the HVAC unit to operate. If the condensate drain line becomes clogged or the drain pan begins to fill with water due to an issue, the water level will rise. When the water reaches the predetermined trip point, the float will lift, causing the magnetically actuated switch to open the circuit. This interruption signals the HVAC system to shut down, preventing the drain pan from overflowing and causing water damage to the surrounding area or property.
മെയിൻ്റനൻസ്
To ensure the continued reliability of your Condensate Cop and HVAC system, regular maintenance is recommended:
- വാർഷിക പരിശോധന: At least once a year, or more frequently if your system is prone to clogs, inspect the drain pan and the Condensate Cop.
- Clean Drain Pan: Ensure the drain pan is clean and free of algae, sludge, or other debris that could obstruct the float's movement or clog the drain line.
- Check Float Movement: Verify that the float within the probe assembly moves freely without sticking. Gently lift and lower it to confirm smooth operation.
- ടെസ്റ്റ് പ്രവർത്തനം: Periodically test the switch by manually lifting the float to ensure it properly shuts down the HVAC unit. Remember to disconnect power before manipulating components if necessary.
- വയറിംഗ് പരിശോധിക്കുക: Check the wiring connections for any signs of wear, corrosion, or loose connections.
ട്രബിൾഷൂട്ടിംഗ്
If your Diversitech CC-1 Condensate Cop is not functioning as expected, consider the following:
- HVAC Unit Not Shutting Off:
- ജലനിരപ്പ് പരിശോധിക്കുക: Ensure the water level in the drain pan is actually reaching the float's trip point.
- Float Obstruction: Verify that the float is not stuck or obstructed by debris, insulation, or the pan itself.
- വയറിംഗ്: Re-check all wiring connections for looseness or incorrect installation. Ensure the switch is correctly wired in series with the low-voltagഇ കൺട്രോൾ സർക്യൂട്ട്.
- സ്വിച്ച് തകരാർ: If all other checks pass, the switch itself may be faulty and require replacement.
- HVAC Unit Shutting Off Prematurely (False Trip):
- Float Position: The float may be set too low, causing it to trip with normal condensate levels or minor fluctuations. Adjust the position higher if possible.
- പാൻ ചലനം: Ensure the drain pan is stable and not shifting, which could cause the float to move erratically.
- വൈബ്രേഷൻ: Excessive vibration from the HVAC unit might be causing the float to bounce and momentarily trip the switch. Ensure the unit is properly isolated from vibrations.
- Wiring Short: Check for any shorts in the low-voltage wiring that could mimic an open circuit.
- No Power to HVAC Unit After Installation:
- സർക്യൂട്ട് ബ്രേക്കർ: Check if the circuit breaker for the HVAC unit has tripped.
- വയറിംഗ്: Double-check all wiring connections, especially where the Condensate Cop was integrated into the circuit. A loose or incorrect connection can prevent power flow.
- Float Position: Ensure the float is in its normal (down) position, allowing the circuit to be closed.
If you are unable to resolve an issue after following these steps, it is recommended to contact a qualified HVAC technician or Diversitech customer support for assistance.
വാറൻ്റിയും പിന്തുണയും
Diversitech products are manufactured to high-quality standards. For specific warranty information regarding your CC-1 Condensate Cop, please refer to the packaging or contact Diversitech Corporation directly. Diversitech is committed to providing exceptional customer support and a comprehensive range of HVAC components.
നിർമ്മാതാവ്: Diversitech Cor.
Webസൈറ്റ്: www.diversitech.com (Note: This is a general placeholder for the official website, please verify the exact URL.)