DAB 60231855

DAB Evosta 2 40-70/130 Circulator Pump Instruction Manual

Model: 60231855 | Brand: DAB

1. ആമുഖവും അവസാനവുംview

The DAB Evosta 2 is an electronic, low-energy consumption circulator pump designed for water circulation in various domestic heating and air conditioning systems. This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Evosta 2 pump.

The Evosta 2 series combines the robustness of mechanical circulators with the advantages of electronic control. It features a synchronous permanent magnet motor, a frequency converter, and an efficiency index (EEI) of ≤ 0.18, ensuring high efficiency and reliability. Its compact design and comprehensive performance make it suitable for replacing older three-speed circulators.

DAB Evosta 2 Circulator Pump
Figure 1: DAB Evosta 2 Circulator Pump. This image shows the main unit with its green and black housing, control panel, and threaded connections.

2 സുരക്ഷാ വിവരങ്ങൾ

പ്രധാനപ്പെട്ടത്: Read all safety instructions before installation or operation. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • ഇൻസ്റ്റാളേഷനും അറ്റകുറ്റപ്പണിയും യോഗ്യതയുള്ള ഉദ്യോഗസ്ഥർ മാത്രമേ നടത്താവൂ.
  • Ensure the power supply is disconnected before performing any work on the pump.
  • The pump operates with hot liquids; allow it to cool before handling to prevent burns.
  • Protect the pump from moisture and direct water spray.
  • Do not operate the pump if it is damaged or if the electrical cable is frayed.
  • The pump is designed for clean, non-viscous, chemically neutral liquids. Do not use with flammable or corrosive liquids.

3. ഉൽപ്പന്ന വിവരണവും സവിശേഷതകളും

The Evosta 2 circulator pump is engineered for optimal performance and durability. Key features include:

  • ഊർജ്ജ കാര്യക്ഷമത: Equipped with a synchronous permanent magnet motor and frequency converter, achieving an EEI ≤ 0.18.
  • കരുത്തുറ്റ നിർമ്മാണം: Cast iron pump body with cataphoresis treatment, wet rotor motor, and ceramic shaft mounted on ceramic bushings lubricated by the pumped liquid.
  • സംയോജിത സംരക്ഷണം: Internal motor protection eliminates the need for external overload protection.
  • ഉപയോക്തൃ സൗഹൃദ നിയന്ത്രണം: A single sequential adjustment button on the control panel simplifies settings.
  • അറ്റകുറ്റപ്പണി ആക്സസ്: Direct access to the crankshaft for potential unlocking.
  • High Protection Rating: സംരക്ഷണത്തിന്റെ IPX5 ഡിഗ്രി.
DAB Evosta 2 Features and Benefits
ചിത്രം 2: ഓവർview of Evosta 2 features, highlighting its energy efficiency (EEI ≤ 0.18) and 5-year warranty. The image also shows different models in the Evosta series.

പമ്പ് സിasing is made of steel, with a technopolymer impeller. The rotor sleeve, stator sleeve, and closing flange are stainless steel. The thrust ring is graphite, and the sealing rings are EPDM. An air bleed plug made of brass is integrated.

DAB Evosta 2 Exploded View and Materials List
ചിത്രം 3: പൊട്ടിത്തെറിച്ചു view of the Evosta 2 pump with a corresponding list of materials for each component, illustrating the internal construction.

4. ഇൻസ്റ്റലേഷൻ

Proper installation is crucial for the pump's performance and longevity. Follow these guidelines:

  • മൗണ്ടിംഗ് സ്ഥാനം: Install the pump with the motor axis horizontal.
  • പൈപ്പ് കണക്ഷനുകൾ: The Evosta 2 40-70/130 is equipped with 1" (G 1") threaded connections. The 1/2" designation refers to the thread intended for connection to 1" to 1/2" reduced female fittings. Verify compatibility with your existing pipes or fittings.
  • വൈദ്യുതി വിതരണം: Connect the pump to a single-phase 1 x 230 V ~ 50/60 Hz power supply. Ensure the electrical installation complies with local regulations.
  • സിസ്റ്റം ഫ്ലഷിംഗ്: Before starting the pump, ensure the system is thoroughly flushed to remove any debris that could damage the pump.
  • വായു ശുദ്ധീകരണം: The pump includes an integrated air bleed plug. After filling the system, open the plug to release any trapped air.

Refer to the dimensional drawings for precise measurements and connection details to ensure proper fitment within your system.

DAB Evosta 2 Dimensional Drawing
Figure 4: Dimensional drawing of the Evosta 2 40-70/130 pump, showing key measurements (in mm) and pump connection details (1" G thread).

5. ഓപ്പറേഷൻ

The Evosta 2 pump features a control panel on the electronic control device cover, allowing for easy adjustment of its functions. The pump offers nine setting options, selectable via the MODE button.

  • ക്രമീകരണം തിരഞ്ഞെടുക്കൽ: Press the MODE button to cycle through the available settings. The selected setting is indicated by six illuminated segments on the display.
  • പ്രവർത്തന രീതികൾ: The pump supports various operating modes, typically including proportional pressure, constant pressure, and constant curve modes, to adapt to different system requirements.
DAB Evosta 2 Operating Modes and Settings
Figure 5: Diagram illustrating the different operating modes (Proportional Pressure, Constant Pressure, Constant Curve) and an example of model designation for the Evosta series.

Consult the specific icons or indicators on your pump's control panel to identify the active operating mode and adjust as needed for your heating or cooling system.

6. പരിപാലനം

Regular maintenance ensures the long-term reliability and efficiency of your Evosta 2 pump.

  • വായു ശുദ്ധീകരണം: Periodically check and, if necessary, open the integrated brass air bleed plug to release any air trapped in the pump. This prevents cavitation and ensures smooth operation.
  • Crankshaft Unlocking: In case of a blockage, the pump provides direct access to the crankshaft for manual unlocking. Refer to the technical diagrams for the exact location.
  • വൃത്തിയാക്കൽ: Keep the exterior of the pump clean and free from dust and debris. Do not use abrasive cleaners.
  • System Fluid: Ensure the pumped liquid remains clean and free of solid substances and mineral oils. Glycol content should not exceed 30%.
  • No Overload Protection Needed: Due to internal motor protection, no external overload protection is required.

7. പ്രശ്‌നപരിഹാരം

If you encounter issues with your Evosta 2 pump, consider the following common problems and solutions:

  • പമ്പ് ആരംഭിക്കുന്നില്ല:
    • വൈദ്യുതി വിതരണവും സർക്യൂട്ട് ബ്രേക്കറും പരിശോധിക്കുക.
    • Ensure the pump is properly connected to the electrical mains.
    • Verify that the motor is not seized. Use the direct access to the crankshaft to attempt manual unlocking if necessary.
  • No Flow or Reduced Flow:
    • Check for air in the system. Bleed air using the integrated plug.
    • Inspect for blockages in the pipes or pump impeller.
    • Ensure valves in the system are open.
    • Verify the selected operating mode and setting are appropriate for the system's requirements.
  • അസാധാരണമായ ശബ്ദം:
    • Noise can indicate air in the system. Purge air.
    • Check for foreign objects in the pump.
    • Ensure the pump is securely mounted and not vibrating excessively.

If problems persist after attempting these solutions, contact qualified service personnel or DAB customer support.

8 സാങ്കേതിക സവിശേഷതകൾ

പരാമീറ്റർമൂല്യം
മോഡൽEvosta 2 40-70/130
നിർമ്മാതാവിൻ്റെ ഭാഗം നമ്പർ60231855
പ്രവർത്തന ശ്രേണി0.4 – 3.6 m³/h with head up to 6.9 meters
ദ്രാവക താപനില പരിധി0 °C മുതൽ +110 °C വരെ
പ്രവർത്തന സമ്മർദ്ദം10 ബാർ (1000 kPa)
സംരക്ഷണ സൂചികIPX5
ഇൻസുലേഷൻ ക്ലാസ്F
ഇൻസ്റ്റലേഷൻMotor axis horizontal
വൈദ്യുതി വിതരണം1 x 230 V ~ 50/60 Hz
Pumped LiquidClean, free of solids/mineral oils, non-viscous, chemically neutral, water-like (max 30% glycol)
പമ്പ് ബോഡി മെറ്റീരിയൽകാറ്റഫോറെസിസ് ചികിത്സയ്ക്കൊപ്പം കാസ്റ്റ് ഇരുമ്പ്
മോട്ടോർ സിasing മെറ്റീരിയൽഉരുക്ക്
ഇംപെല്ലർ മെറ്റീരിയൽടെക്നോപോളിമർ
ഷാഫ്റ്റ് മെറ്റീരിയൽസെറാമിക്
ഭാരം1.86 കി.ഗ്രാം
പാക്കേജ് അളവുകൾ15 x 14 x 10 സെ.മീ
DAB Evosta 2 Performance Curves and Data Table
Figure 6: Performance curves and detailed technical data table for various Evosta 2 models, including flow rate (Q) and head (H) values.

9. വാറൻ്റിയും പിന്തുണയും

The DAB Evosta 2 circulator pump comes with a 5 വർഷത്തെ വാറൻ്റി, ensuring peace of mind regarding its quality and durability. This warranty covers manufacturing defects under normal use conditions.

For technical assistance, warranty claims, or spare parts inquiries, please contact your authorized DAB dealer or customer support. When contacting support, please have your model number (60231855) and purchase date available.

Information regarding the availability of spare parts is not provided in the product data. Please consult your dealer for specific spare part availability.

അനുബന്ധ രേഖകൾ - 60231855

പ്രീview DAB Evosta Series Electronic Circulators: Technical Specifications and Data
Comprehensive technical specifications, features, and data for DAB Evosta 2, Evosta 3, Evosta 2 SAN, and Evosta 2 SOL electronic circulators for domestic heating, cooling, and solar systems.
പ്രീview DAB BPH/BMH/DPH/DMH വെറ്റ് റോട്ടർ സർക്കുലേറ്ററുകൾ: സാങ്കേതിക സവിശേഷതകളും പ്രകടന ഡാറ്റയും
ഹീറ്റിംഗ്, എയർ കണ്ടീഷനിംഗ് സിസ്റ്റങ്ങൾക്കായി രൂപകൽപ്പന ചെയ്‌തിരിക്കുന്ന, DAB-യുടെ BPH, BMH, DPH, DMH സീരീസ് വെറ്റ് റോട്ടർ സർക്കുലേറ്റർ പമ്പുകൾക്കായുള്ള വിശദമായ സാങ്കേതിക സവിശേഷതകൾ, പ്രകടന വക്രങ്ങൾ, ഇലക്ട്രിക്കൽ ഡാറ്റ, മെറ്റീരിയൽ വിവരങ്ങൾ.
പ്രീview DAB EVOSTA സീരീസ് സർക്കുലേറ്റർ പമ്പുകൾ: ഇൻസ്റ്റാളേഷൻ, മെയിന്റനൻസ് ഗൈഡ്
DAB EVOSTA2, EVOSTA3, EVOSTA2 SOL സർക്കുലേറ്റർ പമ്പുകൾ ഇൻസ്റ്റാൾ ചെയ്യുന്നതിനും പരിപാലിക്കുന്നതിനുമുള്ള സമഗ്രമായ ഗൈഡ്. കാര്യക്ഷമമായ തപീകരണ, കണ്ടീഷനിംഗ് സിസ്റ്റങ്ങൾക്കായുള്ള സവിശേഷതകൾ, സാങ്കേതിക ഡാറ്റ, സുരക്ഷ, പ്രവർത്തന രീതികൾ എന്നിവയെക്കുറിച്ച് അറിയുക.
പ്രീview DAB ജനറൽ കാറ്റലോഗ് 2019: ജല സാങ്കേതിക പരിഹാരങ്ങൾ
ബൂസ്റ്റിംഗിനുള്ള പമ്പുകൾ, ചൂടാക്കൽ, മാലിന്യ ജലം, നീന്തൽക്കുളങ്ങൾ, ജലസേചനം എന്നിവയുൾപ്പെടെ വിപുലമായ ജല സാങ്കേതിക പരിഹാരങ്ങൾ ഉൾക്കൊള്ളുന്ന സമഗ്രമായ DAB ജനറൽ കാറ്റലോഗ് 2019 പര്യവേക്ഷണം ചെയ്യുക. റിമോട്ട് കൺട്രോളിനും സ്മാർട്ട് ബിൽഡിംഗ് മാനേജ്മെന്റിനുമുള്ള നൂതനമായ D.Connect സിസ്റ്റം കണ്ടെത്തൂ.
പ്രീview DAB EVOSTA2 SOL Circulator Pump Quick Guide - Installation and Safety
A concise quick guide for DAB EVOSTA2 SOL series circulator pumps, detailing essential safety warnings, installation overview, product specifications, and contact information for domestic heating and solar applications.
പ്രീview DAB EVOPLUS SMALL Multifunction Expansion Module Installation and Maintenance Manual
This manual provides detailed instructions for the installation, use, and maintenance of the DAB EVOPLUS SMALL Multifunction Expansion Module, designed to enhance the functionality of EVOPLUS SMALL circulators.