This manual provides detailed instructions for the installation, operation, and configuration of the GODIYMODULES Digital Analog Signal Input Panel Meter with RS485 Version. This universal analog input display meter is designed to work with various sensors that provide analog output, such as temperature transmitters, frequency converters, motor speed sensors, pressure sensors, and liquid level sensors, to display actual physical quantities.
The meter supports both current and voltage inputs and is adaptable to standard ranges like 0-10V, 2-10V, 0-20mA, and 4-20mA. It can also be configured for other input ranges within 0-10V or 0-20mA by adjusting bias and gain parameters. By default, the display shows a percentage, but users can define their own display range.

ചിത്രം 1.1: മുൻഭാഗം view of the GODIYMODULES Digital Analog Signal Input Panel Meter with RS485 Version, displaying "90.0".
2 പ്രധാന സവിശേഷതകൾ
- Universal analog input display meter compatible with 0-10V, 0-20mA, 2-10V, and 4-20mA signals.
- Supports both current and voltage input types.
- Configurable bias and gain parameters for adapting to various input ranges.
- ഡിഫോൾട്ട് ശതമാനംtage display with user-definable display ranges (F0-2 to F0-4).
- RS485 communication interface for data transmission (on RS485 version).
- Power supply anti-reverse connection and surge protection.
- റേറ്റുചെയ്ത പവർ സപ്ലൈ വോള്യംtage range: DC6~25V (Standard and RS485 versions), DC8~25V (Relay output version).
- Low power consumption: 24V/40mA (Standard/RS485), 24V/50mA (Relay output).
3. പാക്കേജ് ഉള്ളടക്കം
പാക്കേജിൽ ഉൾപ്പെടുന്നു:
- 1 x GODIYMODULES Digital Analog Signal Input Panel Meter (with RS485 Version)
4 സാങ്കേതിക സവിശേഷതകൾ
| ഫീച്ചർ | സ്പെസിഫിക്കേഷൻ |
|---|---|
| മോഡൽ | With RS485 version |
| ഇൻപുട്ട് സിഗ്നൽ തരങ്ങൾ | 0-10V, 2-10V, 0-20mA, 4-20mA (configurable) |
| Power Supply (Standard/RS485) | DC6~25V |
| Power Supply (Relay Output Version) | DC8~25V |
| Power Consumption (Standard/RS485) | 24V/40mA |
| Power Consumption (Relay Output Version) | 24V/50mA |
| അളവുകൾ | 3.94 x 1.98 x 0.79 ഇഞ്ച് |
| ഭാരം | 1.76 ഔൺസ് |
5. ഇൻസ്റ്റലേഷനും വയറിംഗും
Proper wiring is crucial for the correct operation of the meter. Refer to the diagrams and descriptions below for connection details.
5.1. Wiring Terminals Overview

ചിത്രം 5.1: പിന്നിലേക്ക് view of the meter with wiring terminals and label. This image illustrates the physical layout of the connection points.
5.2. Port Signal Description
The following table details the function of each terminal port:
| സിഗ്നൽ | വിശദീകരണം |
|---|---|
| Pwr | Connect to the positive pole of the power supply (Standard/RS485 version: DC6~30V; Relay output version: DC8~30V) |
| ജിഎൻഡി | ശക്തിയും സിഗ്നൽ ഗ്രൗണ്ടും |
| Ai | Analog input signal configuration interface. |
| mA | Current-type analog input signal configuration interface. Short-circuit with Ai for current-type input. |
| 485- (With RS485 version) | RS485 signal negative |
| 485+ (With RS485 version) | RS485 signal positive |
| KA (With relay output version) | Relay normally open contact output port |
| KB (With relay output version) | Relay normally open contact output port |
5.3. Common Wiring Diagrams
Refer to the following diagrams for typical wiring configurations based on your input signal type.

Figure 5.2: Common wiring diagrams. This image shows connections for Voltage Input, Current Input, and Two-Wire Current Sensor configurations.
- വാല്യംtagഇ ഇൻപുട്ട്: പോസിറ്റീവ് വോള്യം ബന്ധിപ്പിക്കുകtage signal to 'Ai' and the negative to 'GND'. Power supply (PWR, GND) is also shown.
- നിലവിലെ ഇൻപുട്ട്: Short-circuit 'Ai' and 'mA', then connect the positive current signal to 'mA' and the negative to 'GND'. RS485 connections (485+, 485-) are also indicated.
- Two-Wire Current Sensor: Connect the sensor's positive output to 'PWR' and its negative output to 'Ai'. The meter's 'GND' is connected to the sensor's ground.
6. Operation and Parameter Settings
This section describes how to operate the meter and configure its various parameters using the front panel buttons.
6.1. ഇൻഡിക്കേറ്റർ ലൈറ്റുകൾ
- "RS485 version":
- R: ഡാറ്റ സ്വീകരണം സൂചിപ്പിക്കുന്നു.
- T: Indicates data transmission.
- "Relay output version": The indicator light illuminates when the relay is closed.
6.2. Button and Display State Transition
The meter features a multi-level menu system for configuration. Use the സെറ്റ്, മുകളിലേക്കുള്ള അമ്പടയാളം, താഴേക്കുള്ള അമ്പടയാളം, ഒപ്പം OK buttons to navigate and adjust settings.

Figure 6.1: Button and digital tube display state transition diagram. This diagram illustrates how to navigate through the menu levels (Monitoring, First-level, Second-level, Third-level) using the SET and OK buttons, and how to modify parameters using the Up/Down arrows.
പ്രത്യേക കുറിപ്പ്: When in the third-level menu, pressing the OK key saves the modified parameter values and returns to the previous menu level, with the parameter number automatically incremented by one. Pressing the സെറ്റ് key returns directly to the previous menu level without saving the modified parameter values. Holding down the Up or താഴേക്ക് key allows the adjustment values to change rapidly.
6.3. Parameter Group F0: Attendant Array Display
These parameters relate to the display and monitoring of the input value.
| പരാമീറ്റർ | പാരാമീറ്ററിൻ്റെ പേര് | Scope and Description | സ്ഥിരസ്ഥിതികൾ | വായിക്കുക/എഴുതുക |
|---|---|---|---|---|
| F0-0 | Collected value monitoring | Monitor the percentage of the current analog input value. Range: 0-100.0% | വായിക്കാൻ മാത്രം | |
| F0-1 | Display value monitoring | In the display value in "Monitoring Menu" is calculated by F0-0, F0-2~F0-4. | വായിക്കാൻ മാത്രം | |
| F0-2 | പ്രദർശന കൃത്യത | The number of decimal places displayed in the "Monitor Menu", range: 0-3. | 1 | വായിക്കുക/എഴുതുക |
| F0-3 | Show minimum | In the "Monitoring Menu", the value corresponding to "acquisition value" is 0%, the range: -1999~9999 | 0 | വായിക്കുക/എഴുതുക |
| F0-4 | Show maximum | In the "Monitoring Menu", the value corresponding to the "Acquisition Value" is 100.0%, the range: 1999~9999 | 1000 | വായിക്കുക/എഴുതുക |
| F0-5 | ഓഫ്ലൈൻ നില | 0: Not disconnected; 1: Disconnected. (Disconnection detection is set by F1-4) (starting from V2.10) | വായിക്കാൻ മാത്രം |
6.4. Parameter Group F1: Analog Configuration Parameters
These parameters configure the analog input signal processing.
| പരാമീറ്റർ | പാരാമീറ്ററിൻ്റെ പേര് | Scope and Description | സ്ഥിരസ്ഥിതികൾ | വായിക്കുക/എഴുതുക |
|---|---|---|---|---|
| F1-0 | ഇൻപുട്ട് തരം തിരഞ്ഞെടുക്കൽ | 0: 0-10V or 0-20mA corresponds to 0-100.0%; 1: 2-10V or 4-20mA corresponds to 0-100.0%, and 0 when it is lower than 2V or 4mA. | 0 | വായിക്കുക/എഴുതുക |
| F1-1 | ഇൻപുട്ട് ഫിൽട്ടർ സമയം | Analog input filter time, range: 0-10.000s. The longer the filtering time, the stronger the filtering. | 0.200 | വായിക്കുക/എഴുതുക |
| F1-2 | ഇൻപുട്ട് നേട്ടം | Range: 0-1000.0%. | 100.0 | വായിക്കുക/എഴുതുക |
| F1-3 | ഇൻപുട്ട് ഓഫ്സെറ്റ് | -99.9~99.9%, with 10V or 20mA as 100.0%. Range: 0.0-100.0%. This value is based on 0-10V or 0-20mA as 0.0-100.0% as a reference (and F1-0 and gain offset are not related). | 0.0 | വായിക്കുക/എഴുതുക |
| F1-4 | Drop detection threshold | The detection is not started if it is less than 0.5, and there is a hysteresis of ±0.3. When the input signal is lower than this value, the meter displays E.OfL. (Starting from V2.10) | 0.0 | വായിക്കുക/എഴുതുക |
| F1-5 | Enter the parameter setting selection | 0: Long press SET button for 3s to enter the parameter setting mode; 1: Keep pressing SET button for more than 3s, and Press OK to enter parameter setting mode | 0 | വായിക്കുക/എഴുതുക |
6.5. Parameter Group F2: Relay Output Dosing (with Relay Output version)
These parameters are applicable only to meters with relay output functionality.
| പരാമീറ്റർ | പാരാമീറ്ററിൻ്റെ പേര് | Scope and Description | സ്ഥിരസ്ഥിതികൾ | വായിക്കുക/എഴുതുക |
|---|---|---|---|---|
| F2-0 | Relay output status configuration | When the output conditions are met, the relay output status: 0: No control (always open); 1: Relay closed; 2: Relay open (not satisfied Closed on condition) | 0 | വായിക്കുക/എഴുതുക |
| F2-1 | കണ്ടീഷൻ തരം | 0: greater than comparison value 1; 1: less than comparison value 2; 2: greater than comparison value 1 and less than comparison value 2. | 0 | വായിക്കുക/എഴുതുക |
| F2-2 | താരതമ്യ മൂല്യം 1 | Range: 0-100.0%. | 50.0 | വായിക്കുക/എഴുതുക |
| F2-3 | താരതമ്യ മൂല്യം 2 | Range: 0-100.0%. | 50.0 | വായിക്കുക/എഴുതുക |
| F2-4 | Hysteresis interval | In order to prevent the relay output from operating frequently near the comparison value, hysteresis interval parameters are introduced. Range: 0.0%-80.0%. | 5.0 | വായിക്കുക/എഴുതുക |
| F2-5 | Relay status when offline | After setting F1-4, when the offline condition is reached, the relay output state. Note: This priority is higher than that of the comparison relay output. 0: Not used; 1: Relay is closed; 2: Relay is disconnected (starting from V2.10) | 0 | വായിക്കുക/എഴുതുക |
Example of Hysteresis Interval: ഉദാample, if F2-1 (Condition type) is set to "0: greater than comparison value 1", F2-2 (Comparison value 1) to 50.0%, and F2-4 (Hysteresis interval) to 5.0%. When the power is on, if the collected value gradually increases and exceeds 50.0%+5.0%/2, the output condition is satisfied. If the collected value decreases, it needs to be less than 50.0%-5.0%/2 to reach the non-output condition.
7. RS485 Communication (with RS485 Version)
This section details the communication parameters and networking for the RS485 version of the meter.
7.1. Parameter Group F7: Communication Parameters and Software Version
| പരാമീറ്റർ | പാരാമീറ്ററിൻ്റെ പേര് | Scope and Description | സ്ഥിരസ്ഥിതികൾ | വായിക്കുക/എഴുതുക |
|---|---|---|---|---|
| F7-0 | പ്രാദേശിക വിലാസം | ശ്രേണി: 1-247 | 1 | വായിക്കുക/എഴുതുക |
| F7-1 | ബൗഡ് നിരക്ക് | 0:1200bps; 1: 2400bps; 2: 4800bps; 3: 9600bps; 4:19200bps; 5: 38400bps | 3 | വായിക്കുക/എഴുതുക |
| F7-2 | ഡാറ്റ ഫോർമാറ്റ് | 0:8,1, None (8 data bits, 1 stop bit, no parity); 1:8,1, Even (8 data bits, 1 stop bit, even parity); 2:8,1, Odd (8 data bits, 1 stop bit, odd parity); 3:8,2, None (8 data bits, 2 stop bits, no parity) | 0 | വായിക്കുക/എഴുതുക |
| F7-3 | പ്രതികരണ കാലതാമസം | Communication response delay time 0~500ms. Use above V1.02 | 5 | വായിക്കുക/എഴുതുക |
| F7-4 | ആശയവിനിമയ തരം | 0: The display table is a Modbus slave, and the user host can read the collected values of the display table; 1: The display table is a network slave between the tables, and can receive the display data of the display table set as the master; 2: The display table is the network host between the tables, and the display value is sent to the slave display table through the broadcast address; 3: The display table is the inter-table networking host, and the display value is sent to the slave by means of address polling. | 0 | വായിക്കുക/എഴുതുക |
7.2. Communication Protocol and Method
The meter uses a Modbus-like protocol for communication. The following describes how to interact with the meter as a slave device.
7.2.1. Reading Collected Values from the Display Table
The user host can read the collected values (F0-0) and display values (F0-1) from the meter. The meter's display range is determined by F0-2 to F0-4. The Modbus register address for F0-0 is 0000H, and for F0-1 is 0001H. The collected value is 0-1000, corresponding to 0-100.0%. The display value is 0-1000, corresponding to the display range set by F0-2 to F0-4. The host can also read and write other parameters (F0-2 to F0-4, F1-0 to F1-5, F2-0 to F2-5, F7-0 to F7-4).
ExampLe: If the collected value F0-0 is 60.0%, the displayed value F0-1 is 60.0. The slave (HXDSBOXAI) response data for reading F0-0 and F0-1 would be:
- Slave address (F7-0): 01H
- Modbus function number: 03H
- Start address (high byte): 00H
- Start address (low byte): 00H
- Read word count (high byte): 00H
- Read word count (low byte): 02G
- CRC (low byte): C4H
- CRC (high byte): 0BH
മുകളിൽ പറഞ്ഞതിൽample, the read F0-0 and F0-1 are 0258H = 600, meaning the collected value F0-0 is 60.0%, and the displayed value F0-1 is 60.0.
7.3. Networking Description Between Tables
Through the network between meters, the display value of the data collected by the master meter can be transmitted to the slave meter for display through RS485. Only one master table can exist in a network, and there can be multiple slave tables. In use, only the master table needs to set the corresponding display range, and the slave table does not need to set the display range.
7.3.1. Main Table Sends Data Through Broadcast Mode Network Diagram

Figure 7.1: Main table sends data through broadcast mode network diagram. This diagram illustrates a master meter (Main table, F7-4 is 2) broadcasting data to multiple slave meters (From table, F7-4 is 1) over an RS485 total line.
7.3.2. Table Network Diagram of Sending Data Through Address Polling

Figure 7.2: Table network diagram of sending data through address polling. This diagram illustrates a primary master meter (F7-0 is 3, F7-4 is 3) polling data from multiple slave meters (F7-0 is 1, F7-4 is 1; F7-0 is 2, F7-4 is 1) over an RS485 total line.
കുറിപ്പ്: When the master meter sends data to the slave meter through address polling, only meters with the same address as the polled address will respond. All other meters will not respond. This ensures targeted communication in a multi-device network.
8. പരിപാലനം
- Keep the meter clean and free from dust and moisture.
- തീവ്രമായ താപനിലയിലോ നേരിട്ടുള്ള സൂര്യപ്രകാശത്തിലോ ഉപകരണം തുറന്നുകാട്ടുന്നത് ഒഴിവാക്കുക.
- Do not use abrasive cleaners or solvents on the display or casing.
- Ensure all wiring connections remain secure. Periodically check for loose connections.
- If the device requires cleaning, use a soft, dry cloth. For stubborn dirt, a slightly damp ഉപകരണത്തിനുള്ളിൽ ദ്രാവകം പ്രവേശിക്കുന്നില്ലെന്ന് ഉറപ്പാക്കാൻ, നേരിയ ഡിറ്റർജന്റ് ഉള്ള തുണി ഉപയോഗിക്കാം.
9. പ്രശ്നപരിഹാരം
- ഡിസ്പ്ലേ ഇല്ല:
- Check power supply connections (PWR, GND) and ensure the voltage is within the specified range (DC6~25V or DC8~25V depending on version).
- Verify that the power supply is active.
- Incorrect Reading:
- Ensure the input signal type (F1-0) is correctly configured for your sensor (0-10V, 2-10V, 0-20mA, 4-20mA).
- Check wiring for the analog input (Ai, mA, GND) to ensure it matches the sensor output.
- Review F1-2 (Input gain) and F1-3 (Input offset) parameters for proper calibration.
- Confirm the display range parameters (F0-3, F0-4) are set correctly.
- RS485 Communication Issues:
- Verify RS485 wiring (485+, 485-).
- Check F7-0 (Local address), F7-1 (Baud rate), and F7-2 (Data Format) parameters to ensure they match the master device settings.
- Ensure the communication type (F7-4) is correctly configured for your network setup (slave, broadcast host, polling host).
- Check the R and T indicator lights for activity.
- Relay Not Activating (Relay Output Version):
- Check F2-0 (Relay output status configuration) to ensure it's not set to "No control".
- Verify F2-1 (Condition type), F2-2 (Comparison value 1), and F2-3 (Comparison value 2) are set to trigger the relay under desired conditions.
- Consider the F2-4 (Hysteresis interval) which might prevent frequent switching.
- Check F2-5 (Relay status when offline) if the meter is in an offline state.
If issues persist after checking these points, consult the manufacturer's support or a qualified technician.